I • Protect the wire and the wiring through hole area for wirings
of the transm i ssion , earth and the remo te contro ller in order
1
to prevent the intrusion of water and small animals into the air
1
conditioner after the system is wired.
• Cut the sealing pad - small (13) into two pieces and wrap each
wiring with each piece.
• Seal the clearance around the wirings with putty or thermal
insulation material (field supply). (If insects and small animals
get into the indoor unit, short circuiting may occur inside the
control box.)
• After all the wiring connections are done, fill in any gaps in the
through holes with putty or insulation (procured locally) to prevent
small animals and insects from entering the unit from outside. (If
any do get in, they could cause short circuits in the control box.)
• Outside the machine, separate the weak wiring (remote controller
cord) and strong wiring (interunit, earth, and other power wiring)
at least 50 mm so that they do not pass through the same place
together. Proximity may cause electrical interference, malfunctions,
and breakage.
_________________________ �
Inter-unit wiring
- - - - - - - - - - - - - - - --.......
,,,,...
Clamping position
1
Se c ure the earth wire
Inter-unit
a nd inter - u n it wir i n g with
wir ing sheath
b o th e d ge s alig n ed.
__ )
-
i
Earth
wire
E
m E
E
:g_E
g
o
LO
£
"'i"
"'i"
� I �
---� �
0
6,
:::::::!
<<Inter-unit wiring (strong electric) / Earth wire>>
_______________________
,
........
Wiring
through-holes
\
I
'- ___ _
Cut off any
excess
�� 3
material after
tightening the
'"""''="'-7rur. inter-unit wiring
and earth wire
..__, � � l:::i_LI,,,.
together.
Earth
wire
\terminal
.
[P r o c e ss in g m ethod of w i r i n g throu gh h o le ]
Transmission wire,
earth wire or remote
controller wire
Sealing pad - Small (13)
Putty or thermal
insulation material
(Filed supply)
Control box lid
Electrical Wiring
1
Diagram Nameplate
(Inside of control box lid)
1
1
1
Fig. 26
/
18
---....,
. .
Wiring through hole
Fig. 25
Remote controller
wiring terminal block