York J10ZJ Instruction Manual page 40

Table of Contents

Advertisement

5167530-JIM-H-0218
Table 14: Smart Equipment™ Economizer Board Details (Continued)
Board
Cover
Label
Label
R
HOT
R
24V~
IN3
OAH
C
COM
R
24V~
IN4
SAH
C
COM
R
24V~
IN5
IAQ
C
COM
R
24V~
IN6
OAQ
C
COM
R
24V~
IN7
FR AIR
C
COM
R
24V~
BLDG
IN8
PRES
40
Description
24 VAC transformer HOT
ANALOG INPUTS Terminal on lower edge of economizer board
24 VAC hot supplied for the outdoor air
humidity sensor
0-10 VDC positive input from the Outdoor Air
Humidity sensor
24 VAC common/0-10 VDC negative for the
outdoor air humidity sensor
24 VAC hot supplied for the supply air humidity
sensor
0-10 VDC positive input from the Supply Air
Humidity sensor
24 VAC common/0-10 VDC negative for the
supply air humidity sensor
24 VAC hot supplied for the indoor air quality
sensor
0-10 VDC positive input from the Indoor Air
Quality sensor
24 VAC common/0-10 VDC negative for the
indoor air quality sensor
24 VAC hot supplied for the outdoor air quality
sensor
0-10 VDC positive input from the Outdoor Air
Quality sensor
24 VAC common/0-10 VDC negative for the
outdoor air quality sensor
24 VAC hot supplied for the air monitoring
station sensor
0-10 VDC positive input from the air monitoring
station sensor
24 VAC common/0-10 VDC negative for the air
monitoring station sensor
24 VAC hot supplied for the building pressure
sensor
0-5 VDC positive input from the Building
Pressure sensor
Function & Comments
24 VAC hot connection to power the economizer board.
Connects through circuit traces to R/24V~ terminals and pins
distributed on the economizer board.
Connects through circuit trace to 24V~ IN pin HOT
OAH parameter reports input status (0-100%H). Used in outdoor
air enthalpy calculation for dual enthalpy economizer free cooling
changeover.
Connects through circuit trace to 24V~ IN pin COM
Connects through circuit trace to 24V~ IN pin HOT
SAH parameter reports input status (0-100%H). Unused in
current control revision.
Connects through circuit trace to 24V~ IN pin COM
Connects through circuit trace to 24V~ IN pin HOT
IAQRange parameter sets the CO2 parts per million measured
by the indoor air quality sensor when it outputs 10 VDC; IAQ
parameter reports input status (0-5000ppm). Used for demand
ventilation functions if the NetIAQ parameter indicates ?Unrel.
Connects through circuit trace to 24V~ IN pin COM
Connects through circuit trace to 24V~ IN pin HOT
OAQRange parameter sets the CO2 parts per million measured
by the outdoor air quality sensor when it outputs 10 VDC; OAQ
parameter reports input status (0-5000ppm). Used for demand
ventilation function when DVent-Mode selection is Diff between
IAQ and OAQ and the NetOAQ parameter indicates ?Unrel.
Connects through circuit trace to 24V~ IN pin COM
Connects through circuit trace to 24V~ IN pin HOT
MOA-Range parameter sets the cubic feet per minute/liters per
second measured by the air monitoring station sensor when it
outputs 10 VDC; Fr Air parameter reports input status (0-
50000CFM/23595lps). Used for economizer minimum position
reset in speed-controlled indoor blower applications.
Connects through circuit trace to 24V~ IN pin COM
Connects through circuit trace to 24V~ IN pin HOT
BldgPres parameter reports input status (-.250-.250"/w/-.062-
.062kPa). Used for modulating power exhaust functions when
ExFType selection is Modulating Damper or Variable Frequency
Fan.