Troubleshooting
The table below lists the self-diagnostic routines. For some of error codes, you must contact an authorized service
centre. If an error occurs during the operation, it is displayed on the outdoor unit PCB LED, both MAIN PCB and
INVERTER PCB.
No.
Error Code
1
E108
Error due to duplicated communication address
Error on room temperature sensor of indoor unit
2
E121
(Short or Open)
3
E122
Error on EVA IN sensor of indoor unit (Short or Open)
Error on EVA OUT sensor of indoor unit (Short or
4
E123
Open)
5
E153
Error on float switch (2nd detection)
6
E154
Indoor fan error
7
E198
Error on thermal fuse of indoor unit (Open)
Communication error between the indoor unit and
outdoor unit (Pre-tracking failure or when the actual
number of indoor units are different from the indoor
unit quantity setting on the outdoor unit)
8
E201
Error due to communication tracking failure after
initial power is supplied (The error occurs regardless
of the number of units.)
Communication error between indoor unit and
9
E202
outdoor unit (When there is no response from indoor
units after tracking is completed)
Communication error between the outdoor unit and
main micom (For PF #4 to #6 controllers, error will
10
E203
be determined from the time when the compressor is
turned on.)
11
E221
Error on outdoor temperature sensor (Short or Open)
12
E231
Error on outdoor COND OUT sensor (Short or Open)
Error on discharge temperature sensor of compressor
13
E251
1 (Short or Open)
14
E320
Error on OLP sensor (Short or Open)
15
E403
Compressor down due to freeze protection control
16
E404
System stop due to overload protection control
17
E416
System stop due to discharge temperature
18
E422
Blockage detected on high pressure pipe
19
E425
Reverse phase or open phase
Meaning
Remarks
Check on repeated indoor unit main address
Indoor unit Room Thermistor Open/Short
Indoor unit EVA_IN Thermistor Open/Short
Indoor unit EVA_OUT Thermistor Open/Short
Indoor unit Float Switch Open/Short Drain Pump
operation Check
Check on indoor unit indoor Fan operation
Thermal Fuse Open Check of indoor unit Terminal
Block
Check indoor quantity setting in outdoor
Check electrical connection and setting between
indoor unit and outdoor unit
Check electrical connection and setting between
outdoor unit MAIN PBA - INVERTER PBA
Check Outdoor sensor Open / Short
Check Cond-Out sensor Open / Short
Check Discharge sensor Open / Short
Check OLP sensor Open / Short
Check Outdoor Cond.
Check Comp. when it starts
-
1. Check if the service valve is open
2. Check for refrigerant leakage (pipe connections,
heat exchanger) and charge refrigerant if necessary
3. Check if there's any blockage on the refrigerant
cycle (indoor unit/outdoor unit)
4. Check if additional refrigerant has been added after
pipe extension
Check whether 3 phase is reversed or opened.