Installation Procedure
7 DIP switch option
ON
1
2
3
4
SW507
∙ SW507 option
On (default)
Switch 1
Disable snow
Switch 2
prevention control
Switch 3
Switch 4
Switch 3
Switch 4
On
On
On
Off
Off
On
Off
Off
(*1) Setting the address manually
a Turn off the air conditioner, press and hold the
K2 switch for a while to enter the Option mode.
(Initial value: 00AU)
– You cannot enter the Option mode when the
air conditioner is running.
48
English
ON
1
2
3
4
SW508
Off
-
-
Enable snow
prevention control
Silence mode option
Operation
Disable Silence mode
Silence mode step 1
Silence mode step 2
Silence mode step 3
b Set the address in SEG3 and SEG4 by pressing the
K2 switch shortly.
Option
SEG1 SEG2 SEG3 SEG4
Channel
0
0
A
address
00 to 15
c Press and hold the K2 switch for a while to save
the address and exit the Option mode. Each
segment will flicker for 3 seconds in the current
display state. Then if you need to change the
address, reset the system, and then repeat all
steps again. Press and hold the K1 switch to exit
without save.
※ If you want to restore the setting to factory default,
press and hold the K4 button while you are in the
option setting mode.
– If you press and hold the K4 button, setting will
be restored to factory default but it doesn't mean
that restored setting is saved.Press and hold the
K2 button. When the segments shows that tracking
mode is in progress, setting will be saved
∙ When snow prevention mode is in use, eco mode
(standby mode) will not work.
∙ SW508 option (AF48MV1MAEEXTC)
On (default)
Switch 1
Auto Silence mode
Switch 2
-
-
Switch 3
Switch 4
-
Function
The address is
U
setautomatically.
The address is
setmanually. You can set
avalue from 0 to 15.
Off