Samsung AF MV1MAEENTC Series User & Installation Manual page 39

Table of Contents

Advertisement

Entire system diagram
Communication cable
Outdoor-to-indoor power cable
Main power cable
Electrical panel
NFB Single
phase 220 to
240V, 50/60Hz
ELB
Outdoor unit
Power wiring diagram
Outdoor-to-indoor
power cable
Model
Outdoor unit
Indoor unit
AF36MV1MAEENTC 50/60
AF36MV1MAEEXTC
AF48MV1MAEENTC 50/60
AF48MV1MAEEXTC
NOTE
1 Voltage range
∙ Units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above
listed range limits
2 Maximum allowable voltage variation between phases is 2%.
3 Wire size & type must comply with the applicable local and national code.
∙ Wire size: Based on the value of MCA.
∙ Wire type: 60245 IEC57(IEC) or H05RN-F(CENELEC) grade or more.
4 MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
5 MCA represents maximum input current.
∙ MFA represents capacity which may accept MCA
∙ Abbreviations
MCA: Min. Circuit Amps. (A)
MFA: Max. Fuse Amps. (A)
Earthing
Ground wire
Indoor unit
1(L) 2(N)
L
N
F1
F2
cable tie
Communication
cable
power supply cable (Single phase
AC 220-240V, should be purchased
on-site)
Outdoor unit
Rated
Hz
Volts
220-240
220-240
Indoor and outdoor unit connection diagram
1(L)
2(N)
Main power cable specifications
The power cable is not supplied with air conditioner.
∙ Select the power supply cable in accordance with
relevant local and national regulations.
∙ Wire size must comply with the applicable local and
national code.
∙ Specifications for local wiring power cord and branch
wiring are in compliance with local cord.
Input Current[A]
Voltage Range
Outdoor(Down_Amp)
Min.
Max.
Cooling
198
264
20.0
198
264
32.0
Indoor unit
Outdoor unit
L
N
1(L) 2(N)
F1
F2
F1 F2
Power supply
Indoor
Total
MCA
MFA
1.0
21.0
21.0
26.3
1.6
33.6
33.6
42.0
English
39