Installation Procedure
Outdoor unit installation request
∙ The suggested space is based on the outdoor temperature
of 35°C while in operation. If the outdoor temperature is
higher than 35°C, secure more space.
∙ Be sure to secure sufficient clearance for a person and air
flow passage.
∙ See the clearances and dimensions in Minimum clearances
for the outdoor unit (page 32) when installing the
outdoor unit.
∙ If you install multiple outdoor units in the same place, be
sure to secure enough space for ventilation and free airflow.
∙ If the space for ventilation is insufficient, the air conditioner
may not perform well as designed.
Minimum clearances for the outdoor unit
When installing 1 outdoor unit
300 or more
300 or
more
300 or
600 or
more
more
600 or more
300 or more
When installing more than 1 outdoor unit
1500 or
600 or
more
more
32
English
(Unit: mm)
1500 or more
1500 or more
2000 or
more
300 or more
1500 or more
(Unit: mm)
3000 or
3000 or
300 or
more
more
more
300 or
600 or
more
more
600 or
more
500 or
more
500 or
more
WARNING
∙ Should adopt bar type louver. Don't use a type of rain
resistance louver.
[Bar type louver]
∙ Louver specifications.
– Angle criteria : less than 20°
– Opening ratio criteria : greater than 80%
300 or
more
600 or
600 or
more
more
1500 or
more
300 or more
600 or
1500 or more
more
300 or
more
300 or
more
[Rain resistance louver]