TECHNICAL DATASHEET
Force-GT DIN Rail Power Supply
24 V 240 W 3 Phase / DRF-24V240W3GBA

Specifications

Input Ratings / Characteristics
Nominal Input Voltage
Input Voltage Range
Nominal Input Frequency
Input Frequency Range
DC Input Voltage Range
*2
Input Current
Efficiency at 100% Load
Average Efficiency
(25%, 50%, 75%, 100%)
Max Power Dissipation
Max Inrush Current (Cold Start)
Power Factor at 100% Load
Leakage Current
*1 For 2-Phase input, see power de-rating on page 3.
*2 Power supply can operate at DC input.
Output Ratings / Characteristics
Nominal Output Voltage
Factory Set Point Tolerance
Output Voltage Adjustment Range
Output Current
Output Power
Line Regulation
Load Regulation
PARD
*4
(20 MHz)
Rise Time
Start-up Time
Hold-up Time
Dynamic Response
(Overshoot & Undershoot O/P Voltage)
Start-up with Capacitive Loads
Functional
*3 For power de-rating from 55°C to 70°C, see power de-rating on page 3.
*4 PARD is measured with an AC coupling mode, 5 cm wires, and in parallel to end terminal with 0.1 μF ceramic capacitor & 47 μF electrolytic capacitor.
2
0% load
100% load
*3
DC OK Relay Contact
3 x 380-500 Vac
3 x 320-575 Vac (3-Phase) or 2 x 340-575 Vac (2-Phase)
50-60 Hz
47-63 Hz
450-800 Vdc
< 0.75 A @ 3 x 400 Vac, < 0.65 A @ 3 x 500 Vac
89.5% typ. @ 3 x 400 Vac & 3 x 500 Vac
89.5% typ. @ 3 x 400 Vac,
89.0% typ. @ 3 x 500 Vac
< 2.7 W @ 3 x 400 Vac & 3 x 500 Vac
< 26.5 W @ 3 x 400 Vac & 3 x 500 Vac
20 A typ. @ 3 x 400 Vac, 25 A typ, @ 3 x 500 Vac
> 0.50 @ 3 x 400 Vac & 3 x 500 Vac
< 3.5 mA @ 3 x 500 Vac
24 Vdc
24 Vdc ± 2%
24-28 Vdc
0-10.0 A
240 W max
< 40 mV (@ 3 x 320-575 Vac input, 100% load)
< 150 mV (@ 3 x 320-575 Vac input, 0-100% load)
< 100 mVpp
50 ms typ. @ nominal input (100% load)
1,000 ms typ. @ nominal input (100% load
20 ms typ. @ 3 x 400 Vac (100% load)
40 ms typ. @ 3 x 500 Vac (100% load)
± 5% @ 3 x 320-575 Vac input, 0-100% load
(Slew Rate: 0.1 A/μs, 50% duty cycle @ 5 Hz to 1 kHz)
10,000 µF Max
Rated: 30 V at 1 A, resistive load. Refer to the details in the
Function section at DC OK Relay Contacts and LED Indicator
Characteristics on page 11.
*1
)