Operating Mode - Delta FORCE-GT Series Technical Data Sheet

Force-gt din rail power supply 24 v 240 w 3 phase
Table of Contents

Advertisement

TECHNICAL DATASHEET
Force-GT DIN Rail Power Supply
24 V 240 W 3 Phase / DRF-24V240W3GBA

Operating Mode

AC Input Operation
The power supply is approved for Star or Wye Networks L1, L2, L3 and PE connections. The nominal input voltage is 380-500 Vac phase
to phase (V
), 380-500 Y 3-Phase or equivalent to 220-289 Vac phase to neutral (V
LL
does not connect with input terminal actually.
DC Input Operation
Step 1.
Use a battery or similar DC source.
Step 2.
Connect either connections of +pole and -pole to L1/L2/L3 as below.
+pole to L1 and –pole to L2
+pole to L1 and –pole to L3
+pole to L2 and –pole to L1
+pole to L2 and –pole to L3
+pole to L3 and –pole to L1
+pole to L3 and –pole to L2
Step 3.
Connect the PE terminal to an earth wire or to the machine ground.
14
Fig. 4
AC Input Operation Connection Diagram
Fig. 5
DC Input Operation Connection Diagram
) voltage system, 220-289 V 3-Phase. The neutral