COOLING PERFORMANCE CAN BE CHECKED WHEN THE OUTDOOR TEMP IS ABOVE 65 DEG F.
TO CHECK COOLING PERFORMANCE, SELECT THE PROPER INDOOR CFM, ALLOW PRESSURES TO STABILIZE. MEASURE INDOOR WET BULB
TEMPERATURE, OUTDOOR TEMPERATURE, LIQUID AND SUCTION PRESSURES. ON THE PLOTS LOCATE OUTDOOR TEMPERATURE (1);
LOCATE INDOOR WET BULB (2); FIND INTERSECTION OF OD TEMP. & ID W.B. (3); READ LIQUID (4) OR SUCTION (5) PRESSURE IN LEFT COLUMN .
EXAMPLE: (1) OUTDOOR TEMP. 82 F.
(2) INDOOR WET BULB 67 F.
(3) AT INTERSECTION
(4) LIQUID PRESSURE @ 600 CFM IS 300 PSIG
(5) SUCTION PRESSURE @ 600 CFM IS 143 PSIG
26
PRESSURE CURVES (Refer below table for models)
INDOOR ENTERING
WET BULB CURVES
TOP TO BOTTOM
71, 67, 63 AND 59 DEG F.
(4)
40
50
60
70
OUTDOOR TEMPERATURE (Degree F)
INDOOR ENTERING
WET BULB CURVES
TOP TO BOTTOM
71, 67, 63 AND 59 DEG F.
(5)
40
50
60
70
OUTDOOR TEMPERATURE (Degree F)
(3)
(1)
80
90
100
110
(3)
(1)
80
90
100
110
ACTUAL:
LIQUID PRESSURE SHOULD BE +/- 10 PSI OF CHART
SUCTION PRESSURE SHOULD BE +/- 3 PSIG OF CHART
(2)
120
OD
ModelA
A5AC3024A1
A5AC3030A1
A5AC3036A1
71
(2)
A5AC3042A1
67
A5AC3048A1
63
59
120
88-A5AC3001-1A-EN
Cooling
@SCFM
750
850
950
1150
1350