Vector TCI-W Manual

Vector TCI-W Manual

Universal controller
Hide thumbs Also See for TCI-W:

Advertisement

Quick Links

TCI-W Universal Controller
Applications
Fan coil units
Heat exchangers
Zoning
General
TCI-W11: 1 independent control loop, 1 internal temperature sensor, 1 universal input (analog/binary/temp), 2
binary outputs, 1 analog output
TCI-W22: 2 independent control loops, 1 internal temperature sensor, 2 universal inputs, 2 binary outputs, 1
analog output.
Internal temperature sensor standard. Add replaceable humidity element as required: AES1-HT-A2 (2%), AES1-
HT-A3 (3%), or AES1-HT-A5 (5%)
Flexible application configuration is made with a parameter-setting routine using the standard operation terminal.
Name
- W
T
C
I
2
Ordering
Stock
Model
code
TCI-W11
40-10 0073
TCI-W11-H
40-10 0162
TCI-W22
40-10 0075
TCI-W22-H
40-10 0077
AES1-HT-A2
40-50 0067
AES1-HT-A3
40-50 0068
AES1-HT-A5
40-50 0069
Temperature sensors: Use Vector Controls NTC sensors to achieve maximum accuracy:SDB-Tn10-20 (duct), SRA-Tn10
(room), SDB-Tn10-20 + AMI-S10 as immersion sensor.
Actuators: Choose modulating actuators with an input signal type of 0-10 V DC or 4-20 mA (Min. and max.signal
limitations may be set with parameters.3-pointpoint actuators with constant running time are recommended.
Binary auxiliary devices (e.g. pumps, fans, on/off valves, humidifiers, etc):Do not directly connect devices that exceed
specified limits in technical specifications – observe startup current on inductive loads.
Doc: 70-00-0158, V1.1, Date: 20160621
Subject to alteration
VAV
Air handlers
Fan, Pump control
-
2
U
Housing
In/Outputs:
Control loops:
Mounting:
Series:
Temperature
Loop
Input
1
1
1
1
2
1
2
1
Features
Universal PID and/or binary control for any analog
input/output signal and range.
Multiple auxiliary functions: heat-cool auto changeover,
automatic enable, setpoint compensation.
Differential, averaging, min and max functions
Cascading of control loops (-W22 type).
Alarm monitoring of low and high limits on all inputs.
Programmable reaction in case of alarm.
Feedback function for inputs and set points.
Functions for dehumidifying, set point shift, cascade
control.
Password protected programmable user and control
parameters.
TCI-W22 also includes
Power Cap protected real-time clock with 48hr power
backup.
7-day programmable schedules, with options including
change of setpoints and direct position of manual
outputs.
Blue backlight.
Humidifiers
Dehumidifiers
Ventilation
Blank = square housing
See table below
1 = 1 control loop, 2 = 2 control loops
W = Wall mounted
TCI
Humidity
Universal
Input
Input
0
1
1
1
0
2
1
2
1
1
1
© Vector Controls GmbH, Switzerland
TCI-W Universal Controller
O
VERVIEW
Radiant heating
Radiant cooling
Pressurization
Binary
Analog
Output
Output
2
1
2
1
rH Sensor 3% acc.
2
1
Clock schedules
2
1
rH Sensor 3% acc.
rH Sensor 2% acc.
rH Sensor 3% acc.
rH Sensor 5% acc.
Option
Standard
Page 1

Advertisement

Table of Contents
loading

Summary of Contents for Vector TCI-W

  • Page 1 40-50 0069 rH Sensor 5% acc. Temperature sensors: Use Vector Controls NTC sensors to achieve maximum accuracy:SDB-Tn10-20 (duct), SRA-Tn10 (room), SDB-Tn10-20 + AMI-S10 as immersion sensor. Actuators: Choose modulating actuators with an input signal type of 0-10 V DC or 4-20 mA (Min. and max.signal limitations may be set with parameters.3-pointpoint actuators with constant running time are recommended.
  • Page 2: Operation

    Front part: 21 x 88 x 88mm (0.8 x 3.5 x 3.5 in.) Power case: ø 58 x 32 mm (ø 2.3” x 1.3”) Weight (including package) TCI-W11 = 250g (8.8 oz), TCI-W22 = 265g (9.3 oz) Doc: 70-00-0158, V1.1, Date: 20160621 © Vector Controls GmbH, Switzerland Page 2 Subject to alteration...
  • Page 3: Dimensions, Mm(Inch)

    Supplying voltages above AC 24 V to low voltage connections may damage the controller or other devices. Connection to voltages exceeding 42 V endangers personnel safety. Doc: 70-00-0158, V1.1, Date: 20160621 © Vector Controls GmbH, Switzerland Page 3 Subject to alteration...
  • Page 4: Display And Operation

    Verify input connections, jumper settings and parameter settings for the input involved. Err3: A function refers to a disabled input. Disable the function or enable the input. Err4: Internal failure. Product must be replaced. Doc: 70-00-0158, V1.1, Date: 20160621 © Vector Controls GmbH, Switzerland Page 4 Subject to alteration...
  • Page 5: Clock Operation

    Available actions blink as you scroll through them, Press OPTION to select one: Pr01 Characteristics of action (e.g. 0–100% for A1) appear (4 bar indicates step 4 complete) 08:00 Press UP/DOWN to select, OPTION to complete Doc: 70-00-0158, V1.1, Date: 20160621 © Vector Controls GmbH, Switzerland Page 5 Subject to alteration...
  • Page 6 Press the POWER to leave the menu. The unit will return to normal operation if no button is pressed for more than 5 minutes. Doc: 70-00-0158, V1.1, Date: 20160621 © Vector Controls GmbH, Switzerland Page 6 Subject to alteration...
  • Page 7: User Configuration

    1–255= Delay for controller to go back to the scheduled Energy Hold OFF, 60(Min) (TCI-W22) ECONOMY, or COMFORT operation mode if the operationmode is changed manually. Doc: 70-00-0158, V1.1, Date: 20160621 © Vector Controls GmbH, Switzerland Page 7 Subject to alteration...
  • Page 8: Input Configuration

    UI2 in – UI1 = UI2 out. It is possible to have multiple differentials on one controller. It is not possible to reverse the subtraction to UI1-UI2. Doc: 70-00-0158, V1.1, Date: 20160621 © Vector Controls GmbH, Switzerland Page 8 Subject to alteration...
  • Page 9: Control Loop Configuration

    Commonly this is used for humidity control to avoid condensation on outside walls or windows in very cold weather. Doc: 70-00-0158, V1.1, Date: 20160621 © Vector Controls GmbH, Switzerland Page 9 Subject to alteration...
  • Page 10 Dead zone h/c set points Economy mode set point shift Set point heating/reverse Set point cooling/direct T [°C, F] PI sequence heating/reverse U [V, mA] PI sequence cooling/direct Doc: 70-00-0158, V1.1, Date: 20160621 © Vector Controls GmbH, Switzerland Page 10 Subject to alteration...
  • Page 11 Offset cooling/reverse Dead zone Economy set point shift Set point heating/reverse Set point cooling/direct T [°C, F] U [V, mA] Binary sequences cooling/direct Binary sequences heating/reverse Doc: 70-00-0158, V1.1, Date: 20160621 © Vector Controls GmbH, Switzerland Page 11 Subject to alteration...
  • Page 12: Output Configuration

    1A03. As the system moves into heating mode, heating airflow increases until it reaches the maximum heating output (1A04), typically 30 to 50% of maximum cooling airflow. Doc: 70-00-0158, V1.1, Date: 20160621 © Vector Controls GmbH, Switzerland Page 12 Subject to alteration...
  • Page 13 State functions (1d01=5)activate the output based on certain conditions with or without a demand for heating or  cooling, in either comfort or standby mode. In Energy Hold OFF mode (EHO) the output will be off. Doc: 70-00-0158, V1.1, Date: 20160621 © Vector Controls GmbH, Switzerland Page 13 Subject to alteration...
  • Page 14 100 seconds as the lifetime of the relays will be shortened with frequent switching. For PWM applications requiring cycle times below 100 seconds we recommend using TCI-W13 with TRIAC outputs. Doc: 70-00-0158, V1.1, Date: 20160621 © Vector Controls GmbH, Switzerland Page 14 Subject to alteration...
  • Page 15: Auxiliary Functions

    Activatecomfort/economy changeoverwith loop configuration parameter(L07). Limit 2 > Limit 1 Limit 1 > Limit 2 Comfort Comfort Mode Mode Standby Standby Limit Limit Limit Limit Input Input Doc: 70-00-0158, V1.1, Date: 20160621 © Vector Controls GmbH, Switzerland Page 15 Subject to alteration...
  • Page 16: Aux Functions

    Limit 1 > Limit 2 Enable Enable Mode Mode Disable Disable Limit Limit Limit Limit Input Input Enable Mode Mode Enable Disable Disable Limit Limit Limit Limit Input Input Doc: 70-00-0158, V1.1, Date: 20160621 © Vector Controls GmbH, Switzerland Page 16 Subject to alteration...
  • Page 17 Limit 1, cool to heat at Limit 2. For binary open/close contact, open is a high value (100%), closed is a low value (0%). Limit 2 > Limit 1 Limit 1 > Limit 2 Heat Heat Mode Mode Cool Cool Limit Limit Limit Limit Input Input Doc: 70-00-0158, V1.1, Date: 20160621 © Vector Controls GmbH, Switzerland Page 17 Subject to alteration...

Table of Contents