AG-S
I
, O
ERIES
NSTALLATION
PERATION AND
Step 6.3.2 Coupling and Tube Assembly (Continued)
(2.3 m ± .25 m)
Step 6.4 Turbulator Installation
Description
Turbulator Adapter 2.5' (76.2 cm)
Turbulator Section 2' (61 cm)
Turbulator Section 2.5' (76.2 cm) (Stainless)
Tube
22 of 57
S
M
ERVICE
ANUAL
7' 6" ± 1'
10' ± 1'
(3 m ± .25 m)
Part Number
03051503
03051504
03051505
91409XXX
Model
AG-40
AG-60
AG-80
AG-100
AG-125
AG-150
AG-175
Total Overall
Tube Length
Install turbulator as specified in the
"Turbulator Installation" chart below.
Turbulator is not required on the AG-175
Turbulator Installation
Model
AG-40
AG-60
AG-80
AG-100
AG-125
AG-150
AG-175
Turbulator section 2.5'
(76.2 cm) (stainless) used in
AG-40 heaters must be in the
section of turbulator nearest
to the burner.
Tube Length
Minimum
10' (3 m)
20' (6 m)
20' (6 m)
30' (9 m)
40' (12 m)
50' (15 m)
60' (18 m)
Tube Section
1st 10' (3 m) Section
2nd 10' (3 m) Section
2nd 10' (3 m) Section
3rd 10' (3 m) Section
4th 10' (3 m) Section
5th 10' (3 m) Section
N/A