Buffer Overflow

Message Archive
All message events for event and alarm messages are automatically stored in a
message archive. The message archive can hold up to 512 message events.
Overflow Warning
When the remaining buffer capacity specified in ProTool (default setting 10%)
is reached, an overflow warning is automatically issued.
Deleting Message
If the message archive has insufficient space to accept any more message
Events In the
events, message events are automatically deleted until the specified remaining
Event of a Buffer
buffer capacity is reached.
Overflow
Deletion is carried out in the following order:
1. The oldest departed messages.
2. Pending messages.
Printout
If Buffer Overflow Message Logging has been specified and a printer is con-
nected and switched on, all deleted alarm and event messages are printed out in
the event of a buffer overflow.
TP27, TP37 Equipment Manual
Release 01/00
For departed event messages, the message events arrival and departure are
deleted. For departed alarm messages, the message events arrival, depar-
ture and acknowledged are deleted.
The oldest pending messages are deleted to make space for the newly re-
ceived events.
Messages
6-23