Characteristics Of S7 Communication - Siemens SIMATIC NET 6GK7 443-5FX02-0XE0 Manual

Table of Contents

Advertisement

Performance Data
Cycle Load Caused by FMS Connections
When calculating the reaction times with FMS connections, the run time of the
function blocks (FBs) in the S7-400 CPU (416-1 see Table 5-4) is the decisive
factor.
The table below shows the cycle load resulting from the available FCs in ms. A
distinction is made between the statuses "job completed" and "job active".
Table 5-4
Status
Component / FB
READ
WRITE
STATUS
REPORT
IDENTIFY
Note
To allow module replacement without a PG, settings on the CPU must be
modified. Open the Properties dialog of the CPU in HW Config; in the "Monitoring
time for" box in the "Startup" tab, check and, if necessary, modify the following
values:
- "Transfer of parameters to modules" (recommended value = 600 *100 ms)
Depending on your system (station configuration), you may need to increase the
following parameter:
- "Ready message from modules"
For more detailed information about supported services and parameters, refer to
the PICS tables (PICS: Protocol Implementation Conformance Statements) in the
manual /4/.
5.4

Characteristics of S7 Communication

The following data is important for operating S7 connections:
B3-14
Job Completed
min
1.2 ms
1.6 ms
1.2 ms
1.6 ms
1.0 ms
1.5 ms
1.7 ms
3.1 ms
1.7 ms
3.1 ms
max
min
1.0 ms
1.0 ms
1.0 ms
1.3 ms
1.3 ms
CP 443-5 Basic for PROFIBUS / Manual Part B3
Job Active
max
2.3 ms
2.7 ms
2.8 ms
4.8 ms
4.8 ms
Release 11/2002
C79000-G8976-C161-04