Performance Data
5.5

Maximum Number of Connections in Total

In total (FDL , FMS , and S7 connections) a maximum of 59 connections can be
operated
As an example, the following multiprotocol configuration was tested:
28 FMS client connections to S7-400/300 with SCC=RCC=1
+ 1 FMS server connection to S7-400 with SCC=RCC=4
+ 1 FMS server connection to S7-300 with SCC=RCC=1
+ 16 FDL connections to S7-400/300
+
+
+
+
Note
If PG or HMI functions are used, a suitable number of S7 connections must be
reserved during configuration!
5.6

Time-of-day Synchronization

The CP 443-5 forwards time-of-day synchronization frames in the following
directions:
1. From the CPU via the CP to PROFIBUS if the local CPU is the time master or
this station is synchronized via a different LAN and the time-of-day
synchronization frame is forwarded via PROFIBUS for the synchronization of
further stations.
2. From PROFIBUS over the CP to the CPU if a remote station is time master, for
example:
- a remote CPU 41x with PROFIBUS interface (for example, CP 443-5)
- a remote PC with CP 5412 / 5613 / 5614
All stations on a PROFIBUS subnet are synchronized with an accuracy of 10 ms.
Note
With transmission rates of < 1.5 Mbps, we recommend that you configure a
synchronization interval of at least 10 s.
B3-16
8 configured S7 connections to S7-400/300
4 unconfigured HMI connections
Time-of-day forwarding