Output terminal function selection (Pr. 190 to Pr. 195)

Pr. 190 "RUN terminal function selection"
Pr. 191 "SU terminal function selection"
Pr. 192 "IPF terminal function selection"
Pr. 193 "OL terminal function selection"
Pr. 194 "FU terminal function selection"
Pr. 195 "ABC terminal function selection"
You can change the functions of the open collector and contact output terminals.
Parameter
Terminal
Factory Setting
Number
Symbol
190
RUN
191
SU
192
IPF
193
OL
194
FU
195
A, B, C
<Setting>
Refer to the following table and set the parameters:
Setting
Signal
Positive
Negative
Name
logic
logic
0
100
RUN
Inverter running
1
101
SU
Up to frequency
Instantaneous power failure or
2
102
IPF
undervoltage
3
103
OL
Overload alarm
4
104
FU
Output frequency detection
Second output frequency
5
105
FU2
detection
Third output frequency
6
106
FU3
detection
7
107
RBP
Regenerative brake pre-alarm
Electronic overcurrent
8
108
THP
protection pre-alarm
9
109
PRG
Programmed mode
10
110
PU
PU operation mode
11
111
RY
Inverter operation ready
12
112
Y12
Output current detection
13
113
Y13
Zero current detection
14
114
FDN
PID lower limit
15
115
FUP
PID upper limit
PID forward-reverse rotation
16
116
RL
output
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Factory-Set Terminal
Function
0
Inverter running
1
Up to frequency
Instantaneous power
2
failure/undervoltage
3
Overload alarm
4
Frequency detection
99
Alarm output
Function
Output during operation when the inverter output
frequency rises to or above the starting frequency.
Refer to Pr. 41 "up-to-frequency sensitivity". (Note
2)
Output when an instantaneous power failure or
undervoltage occurs.
Output while stall prevention function is activated.
Refer to Pr. 42, Pr. 43 (output frequency
detection).
Refer to Pr. 50 (second output frequency
detection).
Refer to Pr. 116 (third output frequency
detection).
Output when 85% of the regenerative brake duty
set in Pr. 70 is reached.
Output when the cumulative electronic
overcurrent protection value reaches 85% of the
preset level.
Output in the programmed mode. (Note 3)
Output when the PU operation mode is selected.
Output when the inverter can be started by
switching the start signal on or while it is running.
Refer to Pr. 150 and Pr. 151 (output current
detection).
Refer to Pr. 152 and Pr. 153 (zero current
detection).
Refer to Pr. 128 to Pr. 134 (PID control).
144
PARAMETERS
Related parameter
Pr. 76 "operation mode selection"
Setting Range
0 to 199, 9999
0 to 199, 9999
0 to 199, 9999
0 to 199, 9999
0 to 199, 9999
0 to 199, 9999
Operation
Pr. 66, Pr. 148,
Pr. 79, Pr. 200
Pr. 17 = 0 to 3
Pr. 150, Pr. 151
Pr. 152, Pr. 153
Related
parameter

Pr. 41

Pr. 22, Pr. 23,
Pr.1, Pr. 149,
Pr. 154
Pr. 42, Pr. 43
Pr. 50
Pr. 116
Pr. 70
Pr. 9
to Pr. 231

Pr. 128 to
Pr. 134

Advertisement

Table of Contents
loading

Table of Contents