4.15.6 Output terminal function selection (Pr. 190 to Pr. 196)

You can change the functions of the open collector output terminal and relay output terminal.
Parameter
Number
190
RUN terminal
function selection
191
SU terminal function
selection
192
IPF terminal function
selection
193
OL terminal function
selection
194
FU terminal function
selection
195
ABC1 terminal
function selection
196
ABC2 terminal
function selection
..............Specifications differ according to the date assembled. Refer to page 491 to check the SERIAL number.
(1) Output signal list
 You can set the functions of the output terminals.
 Refer to the following table and set the parameters: (0 to 99: Positive logic, 100 to 199: Negative logic)
Setting
Signal
Positive
Negative
Name
Logic
Logic
0
100
RUN
Inverter running
1
101
SU
Up to frequency
Instantaneous power
2
102
IPF
failure/undervoltage
3
103
OL
Overload alarm
Output frequency
4
104
FU
detection
Second output
5
105
FU2
frequency detection
Third output frequency
6
106
FU3
detection
Regenerative brake
7
107
RBP
pre-alarm
Electronic thermal O/L
8
108
THP
relay pre-alarm
10
110
PU
PU operation mode
Inverter operation
11
111
RY
ready
Output current
12
112
Y12
detection
Initial
Name
Value
0
1
Open
collector
2
output
terminal
3
4
99
Relay
output
terminal
9999
Function
Output during operation when the inverter
output frequency rises to or above Pr. 13
Starting frequency.
Output when the output frequency is reached
*1
to the set frequency.
Output at occurrence of an instantaneous
power failure or when undervoltage protection
is activated.
Output while stall prevention function is
activated.
Output when the output frequency reaches
the frequency set in Pr. 42 (Pr. 43 for reverse
rotation).
Output when the output frequency reaches
the frequency set in Pr. 50.
Output when the output frequency reaches
the frequency set in Pr. 116.
Output when 85% of the regenerative brake
duty set in Pr. 70 is reached.
Output when the electronic thermal relay
function cumulative value reaches 85% of the
trip level.
(Electronic thermal relay function protection
(E.THT/E.THM) activates, when the value
reached 100%.)
Output when the PU operation mode is
selected.
Output when the inverter power is turned ON,
then output after reset process is completed
(when the inverter can be started by switching
the start signal ON or while it is running).
Output when the output current is higher than
the Pr. 150 setting for longer than the time set
in Pr. 151.
Function assignment of external terminal and control
Initial signal
RUN (inverter running)
0 to 8, 10 to 20, 25 to 28, 30 to 36,
SU (up to frequency)
39, 41 to 47, 55, 64, 70, 84, 85, 90
to 99, 100 to 108, 110 to 116, 120,
IPF (instantaneous power
failure, undervoltage)
125 to 128, 130 to 136, 139,
141 to 147, 155, 164, 170, 184,
OL (overload alarm)
185, 190 to 199, 9999
FU (output frequency
detection)
0 to 8, 10 to 20, 25 to 28, 30 to 36,
ALM (fault output)
39, 41 to 47, 55, 64, 70, 84, 85, 90,
91, 94 to 99, 100 to 108, 110 to 116,
120, 125 to 128, 130 to 136, 139,
No function
141 to 147, 155, 164, 170, 184,
185, 190, 191, 194 to 199, 9999
Operation
Setting Range
Related
Refer to
Parameters
Page
-
246
Pr. 41
250
Pr. 57
270
Pr. 22, Pr. 23,
Pr. 66, Pr. 148,
152
Pr. 149, Pr. 154
Pr. 42, Pr. 43
250
Pr. 50
250
Pr. 116
250
Pr. 70
211
Pr. 9
187
Pr. 79
321
-
246
Pr. 150, Pr. 151
252
243
4