Output current detection function (Pr. 150, Pr. 151)

Pr. 150 "output current detection level"
Pr. 151 "output current detection time"
If the output current remains higher than the Pr. 150 setting during inverter operation for longer than the
z
time set in Pr. 151, the output current detection signal (Y12) is output from the inverter's open collector
output terminal.
(Use any of Pr. 190 to Pr. 195 to assign the terminal used for Y12 signal output.)
Parameter
Factory Setting
Number
150
150%
151
0
<Setting>
Refer to the following list and set the parameters:
Parameter Number
Set the output current detection level.
150
100% is the rated inverter current.
Set the output current detection time. Set a period of time from when the output current rises to or above the
151
Pr. 150 setting to when the output current detection signal (Y12) is output.
Note: 1. Once switched on, the output current detection signal is held on for at least 100ms.
2. This function is also valid during execution of the online or offline auto tuning.
3. When the terminal functions are changed using Pr. 190 to Pr. 195, the other functions may be
affected. Confirm the functions of the corresponding terminals before making settings.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Setting Range
0 to 200.0%
0 to 10 s
Minimum 100ms
OFF
ON
Output current
detection signal
Output (I)
Pr.150
Pr.151
Description
135
PARAMETERS
Related parameters
Pr. 190 to Pr. 195
(output terminal function selection)
OFF
Time (t)