Connecting Power Cord with Three-Wire
Plug
NOTE: Four-wire cord is required for new branch-
circuit installations, mobile homes or where codes
do not permit grounding through neutral.
NOTE: The power cord is NOT supplied with the
electric dryer. Type of power cord and gauge of wire
must conform to local codes and instructions.
The method of wiring the dryer is optional and subject
to local code requirements.
NOTE: Connect the dryer to the power supply with the
MAXIMUM RATED VOLTAGE listed on the nameplate.
120 ± 12
V.A.C.
240 ± 12
V.A.C.
NOTE: Use COPPER WIRE only.
Shorter than 15 ft. (4.5 m) – use 10 AWG
Longer than 15 ft. (4.5 m) – use 8 AWG
1
3 Wire Grounded Neutral 120/240 Volt, 60 Hertz
AC 1 Phase Service Entrance Switch Box
(Refer to NOTE above)
2
30 Ampere Fuses or Circuit Breaker
3
Neutral Wire
1. Disconnect power to dryer.
2. Remove access cover from rear of dryer.
Figure 14
20
A typical
INTERMEDIATE
30-Amp
FUSE BOX (may
Three-Wire
be omitted if
Receptacle
service entrance
NEMA Type
box is fused)
10-30R
WALL
RECEPTACLE
120 ± 12
V.A.C.
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
POWER SUPPLY
L1
L2
POWER CORD CONNECTION
4
Metallic or Non-Metallic Sheathed Cable
(Copper Wire Only)
5
Power Cord (Not supplied with dryer)
6
Neutral
7
Terminal Block in Dryer
Figure 13
3. Use a strain relief and insert end of power cord
through power supply hole.
D695I
POWER SUPPLY
1
2
3
INTERMEDIATE
SHUT-OFF BOX
(may or may not
4
5
6
7
L1
L2
DIRECT CONNECTION
Figure 15
be fused)
D816I
D696I
510977