Uc800 Software Installation And Configuration - Trane RTHD Installation Instructions Manual

Afdr retrofit air-cooled adaptive frequency drive
Hide thumbs Also See for RTHD:
Table of Contents

Advertisement

Installation
Figure 76. AFD pin location
Pins 61,
68, 69
®
(Modbus
)
1K14 Relay Connections
9. Using 16 AWG, make the following connections to relay
1K14 listed in
Table
15.
Table 15. Pin-out, relay 1K14
Terminal –
Relay 1K14
Description
A1
Coil, 115V "hot"
A2
Coil, 115V com
9
N/O contact
5
N/O contact
NOTICE
Compressor Damage!
Before connecting power wire to the motor terminals,
with the motor terminal jumpers removed, verify proper
phasing between the drive and motor terminals with an
ohmmeter for all connections. Improper phasing
occurs between the drive and motor terminals can
cause compressor damage.
UC800 Software Installation and
Configuration
Note: The software upgrade process requires that the
UC800 ether have no application code already
installed, or if an application is existing, that the
controller be in the Stop mode and that the compressor
and the pumps have been shut off. TU will enforce this
requirement with pop-up messages at the appropriate
step in the process, but it is best to Stop the chiller
before the software upgrade process begins.
1. Connect the service laptop computer to the target RTHD
UC800 using an A/B type USB cable. Launch Tracer
service tool software in the service computer. If no shortcut
exists, the program can be found in Programs > Trane >
Tracer TU.
50
®
Modbus
Mating Connection Description
To High Pressure
1X5-3
Cutout, NC (RED
Wire)
1X5-8 thru 11
To 115V common
Pin 37 AFD Drive
Safe Stop
Pin 12 AFD Drive
24V out
®
Figure 77.
2. After Tracer TU is launched, the Startup Task Panel dialog
box appears; refer to
and then click Connect button.
Important:
Tracer TU version 9.0.322 is required. If that
version or newer is not already installed, refer
to
"Pre-Installation," p. 18
obtain and upgrade Tracer TU.
Figure 78.
TU
Figure
78. Select Direct Connection
for details on how to
SO-SVN048A-EN

Advertisement

Table of Contents
loading

Table of Contents