Pre-Installation

Required Tools

Normal service tools are required to perform the majority of the
work. A service technician with a well stocked tool chest should
have the right tools to perform the job. In addition to the normal
service tools and hardware, the following is a partial list of
specific field supplied hardware/software components and
special tools that are also required to perform the display
retrofit:
RS-232 male DB9 to female DB9 pin to pin serial cable to
connect the DynaView™ to a PC or laptop computer
Note:
– The cable must NOT be a null-modem cable.
– The cable must be less than 50 feet in length.
Type A to Type B USB cable to connect the Tracer
controller to a PC or laptop computer
A PC or laptop computer equipped with the following:
– KestrelView™ service software, version 14.0 or newer
– Tracer TU service software, version 9.0.322 or newer
Table 2.
Components – close mount 460 volts
Kit Part Number
Mnemonic
RNG02318
BRD02944
HLD00579
RAL01142
127500010001
CAB01534
CAB01153
CAB01150
18
®
UC800
Part Number
Close Mount Components
X13640734010
531405110100
531405470100
531405480100
X13650733060
X13260721020
X13260722010
X13500224070
X13491363010
507117910001
507117920001
507117930001
507117960001
507117970001
X19080029040
X19010309470
X19051625030
X19051624030
X19051623020
X39002507010
507117810001
SO-SVN048*-EN
507117830001
BAS-SVX54*-EN
507118200001
X39003759010
– RTHD UC800 firmware build 3.03 or later (refer to
"Preparing Tracer® TU on the Service Computer,"
p.
25)
South pole magnet screwdriver (TOL01343)
Electronics vacuum
Drill
3/16-inch drill bit
3/8-inch drill bit for display arm
2.5-inch hole saw (close mount kit only)
Phillips screwdriver
Wrench for fastening the bolts for the panel
Wire cutter for large and small gage wire
Vacuum pump
Oil pump
Impact drill for concrete

Parts

Description
Choke Core M-116
Core Support Bracket
Buss Bar, Formed (for motor connection)
Buss Bar, Straight (for motor connection)
Dual Relay output Ref 1A8 (latest revision)
Relay, 4PDT, 120VAC, 8amps
Relay Socket, 4PDT, Din rail mount
Din rail 4inch
Din Rail End Stop
Strut Channel, 1.625-inch x 1.625-inch x 5ft (black color)
Strut Channel Base, 4-inch x 6-inch (black color)
Strut Channel L Bracket
.75-inch conduit connector 90 degree
.75-inch Conduit Connector Straight
0.75-inch conduit - AFD/relay signal wires
single conductor cable - 16awg UL 1230 blk
Global harness Female to Amp connector 78.74-inch
Global harness Male to Amp connector 78.74-inch
Extension Harness - 78.74-inch
Label, Warning (AFD)
Label, Nameplate
KIT IOM (supplied by Trane)
Schematics Printed on mylar
Drive IOM
AFD Label
Label, Technical support
Qty
5
1
2
1
1
2
2
1
4
1
1
1
1
1
20 ft
125 ft
1
1
1
1
1
1
1
1
1
1