Operating Principles; Control Sequences Of Operation; Occupied/Unoccupied Switching; Compressor Lead/Lag - Trane SCWM Series Installation, Operation And Maintenance Manual

Modular self-contained 25 to 80 tons
Table of Contents

Advertisement

Operating Principles

Control Sequences of Operation

Occupied/Unoccupied Switching

There are three ways to switch occupied/unoccupied:
1. Field-supplied contact closure (hardwired binary input
to field wiring terminal block (2TB3)) — This input
accepts a field supplied switch or contacts closure such
as a time clock. Open Contacts = Unoccupied and
Closed Contacts = Occupied.
2. BACnet® MSTP control system can control the
occupied/unoccupied request of the unit.
3. Through the TD7 Display via the on-board schedule.

Compressor Lead/Lag

Compressor lead/lag is present in the controls for all units
with two or more fixed speed compressors. Only
Compressors 2 and 3 rotate. Balanced run hours is
achieved by changing the fixed speed compressors
sequence number when commanded to rotate.
Variable speed compressor A is always the first stage on
and last stage to turn off for mechanical cooling.

Emergency Stop Input

A binary input is provided on the unit's field wiring terminal
block (2TB3) for installation of a field-provided switch or
contacts to immediately shutdown all unit functions. An
open contact will indicated an emergency shutdown
condition exist and shut down the unit and generate a
manual reset alarm. A closed set of contacts will indicate a
normal condition. After the contacts are closed, the manual
reset alarm must be cleared to resume unit operations.

External Auto/Stop Input

A binary input is provided on the unit's field wiring terminal
block (2TB3) for installation of a field-provided switch or
contacts to safely shutdown all unit functions. An Open
contact will indicate a Stop condition exist and the unit will
shutdown and generate an automatic reset alarm. A
Closed contact will indicate an Auto condition and allow the
unit to operate.

Local Auto Stop

A binary value is located on the TD7 which allows the user
to start and stop the unit in a safe manner for maintenance.
On the TD7 home screen in the upper right hand corner the
unit can be put into Auto to perform normally or Stop to
perform a controlled shutdown and keep the unit off.

Water Flow Control

With compatible piping configurations, the unit can be
configured to provide variable water flow with the water
regulating valve option only, which maximizes energy
saving by unloading the water pumping system.
48

Head Pressure Control

Water-cooled condensers: Units that are ordered with the
optional flow control valves and configured for variable
water flow will modulate a water valve to maintain a user-
defined condensing pressure setpoint and compressor
refrigerant pressure differential. Condensing pressure and
pressure differential will be referenced utilizing factory
installed suction and discharge pressure sensors located at
each condenser.

Water Purge

This user-definable feature allows the user to select a
purge schedule to automatically circulate water through the
economizer and condensers periodically during non-
operational times. This allows fresh chemicals to circulate
in waterside heat exchangers.
Supply Air Temperature Control
Unit Sequence of Operation
Discharge Air High Temp Limit Software
Alarm (Software)
When the Discharge Air Temperature is above the
Discharge Air High Temperature Cutout setpoint of 100
degrees for 5 minutes, the unit will perform a controlled
shutdown. A Manual Reset alarm will be generated and
need to be cleared before the unit can resume operating.
Condenser Water Low Temperature
Alarm (Software)
When either the entering or leaving condenser water
temperature is below the Condenser Water Low
Temperature cutout setpoint of 35 degres for 5 minutes, the
unit will perform a controlled shutdown. All Condenser
water valves will be commanded open if installed, and a
manual reset diagnostic will be generated and need to be
cleared before the unit can resume operation.
Leaving Air Low Temperature Alarm
When the Discharge Air Temperature is below the
Discharge Air Temperature Cutout for 5 minutes, the unit
will perform a controlled shutdown. A Manual Reset alarm
will be generated and need to be cleared before the unit
can resume operation.

Occupied Fan Operation

When all alarms are cleared, the unit is occupied, and the
local auto stop is in auto, all fans that are available will start
up and operate at 30% speed for 45 seconds. The fans will
then release to control to the duct static pressure setpoint.
The fans will modulate to maintain the Duct Static Pressure
at the Duct Static Pressure Setpoint. The fans are
commanded off during the unoccupied mode.