16.6 ESP curve: Indoor unit

EPRA14~18D + ETSH/X(B)16P30+50E
Daikin Altherma 3 H HT ECH₂O
4P679467-1C – 2023.07
Note: A flow error will occur when the minimum water flow rate is not reached.
For E models:
A (kPa)
120
100
80
60
40
20
0
10
0
5
D E
A External static pressure in the space heating/cooling circuit
B Water flow rate through the unit in the space heating/cooling circuit
C Operation range
D Minimum flow during normal operation
E Minimum flow during backup heater operation
F Minimum flow during cooling operation
G Minimum flow during defrost heater operation
For E7 models:
A (kPa)
120
100
80
60
40
20
0
10
0
5
D E
A External static pressure in the space heating/cooling circuit
B Water flow rate through the unit in the space heating/cooling circuit
C Operation range
D Minimum flow during normal operation
E Minimum flow during backup heater operation
F Minimum flow during cooling operation
G Minimum flow during defrost heater operation
Dashed lines: Operation area is extended to lower flow rates only in case the unit
operates with heat pump only. (Not in startup, no backup heater operation, no
defrost operation.)
Notes:
Selecting a flow outside the operating area can damage the unit or cause the unit
to malfunction. See also the minimum and maximum allowed water flow range in
the technical specifications.
Make sure water quality complies with EU directive 2020/2184.
C
15
20
25
30
35
F
G
C
15
20
25
30
35
F
G
16
Technical data
|
40
45
50
B (l/min)
40
45
50
B (l/min)
Installer reference guide
291