Carrier 58TP0B Installation, Start-Up, Operating And Service And Maintenance Instructions page 39

Table of Contents

Advertisement

58TP0B/58TP1B: Installation, Start-up, Operating and Service and Maintenance Instructions
CAUTION
!
FURNACE DAMAGE HAZARD
Failure to follow this caution may result in:
-
Overheating the heat exchangers or condensing flue gases in
heat exchanger areas not designed for condensate.
-
Shortened furnace life
-
Component damage.
Temperature rise must be within limits specified on furnace rating plate.
Recommended operation is at midpoint of rise range or slightly above.
The furnace must operate within the temperature rise ranges specified on
the furnace rating plate. Do not exceed temperature rise range specified
on unit rating plate. Determine the temperature rise as follows:
1. Place thermometers in return and supply ducts as near furnace as
possible. Be sure thermometers do not see heat exchanger so that
radiant heat does not affect readings. This practice is particularly
important with straight-run ducts.
2. When
thermometer
readings
temperature from supply-air temperature to determine air
temperature rise.
NOTE: The temperatures read by the RAT and SAT sensors connected
to the control board can be displayed during heating and cooling
operation by enabling this feature in the (t°) menu item. See
Select F for Fahrenheit or C for Celsius. When enabled, the display will
cycle through the current operating mode, SAT, RAT, and temperature
differential. If displayed SAT value does not agree with measured
values, relocate SAT sensor farther away from furnace or after a bend in
the ductwork.
NOTE: Temperature rise can be determined for low-heat and high-heat
operation by locking the furnace in each mode of operation. The mode of
operation is based on the (Htt) setting on the furnace control board.
3. If temperature rise is outside this range, proceed as follows:
a. Check gas input for low- and high-heat operation.
b. Check derate for altitude, if applicable.
c. Check all return and supply ducts for excessive restrictions
causing static pressure greater than 0.5 in. w.c.
To lock the furnace in low heat:
1. On the 3 digit display, navigate to (Htt) and select (2St) to lock
the furnace in low-heat operation. See
2. Connect a jumper across R and W/W1 at the thermostat terminals at
the furnace control.
3. Allow the burners to ignite and the blower to turn on.
4. Allow the supply temperature to stabilize and verify the proper rise
range.
If the temperature rise is too high or too low in low heat:
1. Remove jumpers from R and W/W1.
2. Wait until the blower off delay is completed.
3. Remove blower door.
4. Refer to the FURNACE CONTROL PROGRAMMING AND
NAVIGATION section of this manual for instructions on adjusting
the blower speed.
5. Replace blower door.
6. Re-check low heat temperature rise.
To lock the furnace in high heat:
1. Connect a jumper across R and W/W1 and W2 at the thermostat
terminals at the furnace control.
2. Allow the burners to ignite and the blower to turn on.
b. Disconnect power to furnace and remove vent connector from
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
stabilize,
subtract
return-air
Fig.
45.
Fig. 45
and
Fig.
46.
3. Allow the supply temperature to stabilize and verify the proper rise
range.
If the temperature rise is too high or too low in high heat:
1. Remove jumpers from R and W/W1 and W2.
2. Wait until the blower off delay is completed.
3. Remove blower door.
4. Refer to the FURNACE CONTROL PROGRAMMING AND
NAVIGATION section of this manual for instructions on adjusting
the blower speed.
5. Replace blower door.
6. Re-check low heat temperature rise.
After the temperature rise has been verified:
1. Remove jumpers from thermostat terminals.
2. Allow the blower off delay to complete.
3. On the 3 digit display, navigate to (Htt) and select (1St) or (2St)
to depending on thermostat type. See
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Blower access door switch opens 115-V power to control. No
component operation can occur unless switch is closed. Caution must
be taken when manually closing this switch.
!
FIRE HAZARD
Failure to follow this warning could result in personal injury, death,
and/or property damage.
Reinstall manifold pressure tap plug in gas valve to prevent gas leak.
!
FURNACE OVERHEATING HAZARD
Failure to follow this caution may result in reduced furnace life.
Recheck temperature rise. It must be within limits specified on the
rating plate. Recommended operation is at the mid-point of rise range
or slightly above.
Check Safety Controls
The flame sensor, gas valve, and pressure switch were all checked in the
Start-up procedure section as part of normal operation.
1. Check Main Limit Switch
This control shuts off combustion system and energizes
air-circulating blower motor, if furnace overheats. By using this
method to check limit control, it can be established that limit is
functioning properly and will operate if there is a restricted
return-air supply or motor failure. If limit control does not function
during this test, cause must be determined and corrected.
a. Run furnace for at least 5 minutes.
b. Gradually block off return air with a piece of cardboard or sheet
metal until the limit trips.
c. Unblock return air to permit normal circulation.
d. Burners will re-light when furnace cools down.
2. Check draft safeguard switch. The purpose of this control is to
cause the safe shutdown of the furnace during certain blocked vent
conditions.
a. Verify vent pipe is cool to the touch.
furnace vent elbow.
39
Fig. 45
and
Fig.
46.
WARNING
WARNING
WARNING

Advertisement

Table of Contents
loading

This manual is also suitable for:

58tp1b

Table of Contents