Table 4. Electric Heater and Cord Information, PTEG and PTHG Sizes 12 and 15
Voltage:
Amps:
15
Heater Size:
2.5 kW
Plug Layout:
NEMA Plug:
6-15P
Cord #
(a)
:
PWR00286
(a)
Power cord does not ship with the unit.

Power Cord Protection

The power cord for 230/208V units provide protection
from fire. The unit power automatically disconnects
when unsafe conditions are detected. Power to the unit
can be restored by pressing the reset button on plug
head. Upon completion of unit installation for 230/208V
models, an operational check should be performed
using the TEST/RESET buttons on the plug head.
PTAC-SVX004A-EN
230 Vac
20
30
3.5 kW
5.0 kW
6-20P
6-30P
PWR00288
PWR00290
15
2.5 kW
7-15P
PWR00287
N N o o t t e e : : Models with 265V do not incorporate this feature
because they require use of an electrical sub-
base accessory. Connection to a wall socket is
not permitted for 265V units. All 265V units must
be hard wired using the hard wire kit or make
use of the plug-in receptacle in the standard sub-
base.
E E l l e e c c t t r r i i c c a a l l
265 Vac
20
30
3.5 kW
5.0 kW
7-20P
7-30P
PWR00289
PWR00291