Trane ProSpace PTEG0701GAA Installation, Operation And Maintenance Manual page 29

Packaged terminal air conditioner (ptac) r32 ac/heat pump with electric heat
Table of Contents

Advertisement

connection board and then remove the middle
connection board.
19. Remove the screw holding the cable cross and then
remove the cable cross.
W W A A R R N N I I N N G G
R R e e c c o o v v e e r r R R e e f f r r i i g g e e r r a a n n t t ! !
P P l l e e a a s s e e b b e e s s u u r r e e t t o o r r e e c c o o v v e e r r r r e e f f r r i i g g e e r r a a n n t t p p e e r r s s t t a a n n d d a a r r d d
p p r r o o c c e e d d u u r r e e s s a a n n d d g g u u i i d d e e l l i i n n e e s s b b e e f f o o r r e e p p r r o o c c e e e e d d i i n n g g w w i i t t h h
a a d d d d i i t t i i o o n n a a l l s s t t e e p p s s b b e e l l o o w w . .
20. Unsolder the spot weld between the 4-way valve
and the compressor, condenser, and the
evaporator. Remove the 4-way valve.
21. Remove three (3) nuts holding the compressor and
then remove the compressor.
PTAC-SVX004A-EN
22. Unsolder the spot weld between the capillary sub-
assembly and condenser Remove the capillary.
23. Remove six (6) screws holding the guide loop sub-
assembly and then pull upwards to remove the
guide loop sub-assembly.
24. Remove the nuts holding the axial flow blade and
the pull outwards to remove the axial flow blade.
25. Remove four (4) screws holding the motor and then
remove the motor.
D D i i s s a a s s s s e e m m b b l l i i n n g g t t h h e e U U n n i i t t