rough framing - before appliance installation

EN
4.1

minimum framing dimensions

E
minimum framing
E
F
G
H
I
Horizontal vent sections: A minimum clearance of 3" (76mm) on the top outside of the enclosure and 2"
(51mm) on the sides and bottom outside of the enclosure all around the vent pipe on all horizontal runs to com-
bustibles is required. Horizontal vent sections within enclosures require a minimum clearance of 6"(152mm) at the
top of the vent pipe.
Vertical vent sections: A minimum of 1" (25mm) all around the vent pipe on all vertical runs to combustibles is
required except for clearances in appliances enclosures. Vertical vent sections within enclosures require a mini-
mum clearance of 1" (25mm) around the vent pipe.
22
W415-4121 / B / 04.20.23
6" (15.2cm) min.
F
Do not put objects in front of the
appliance (minimum distance of 4 feet)
TLV50
65 13/16" (167.2cm) 77 13/16" (197.6cm) 89 13/16" (228.1cm)
72 1/4" (183.5cm)
102 3/16" (259.5cm) 114 1/8" (289.9cm)
H
TLV62
20 1/8" (51.1cm)
80 11/16" (205cm)
18 3/16" (46.2cm)
126 1/8" (320.4cm)
G
1" (2.54cm) min.
F
I
TLV74
89 1/4" (226.6cm )