PDX Series

Control Timings

Ignition State
Pre-purge
Trial for Ignition
Flame Stabilization Period
Inter-purge
Flame Failure Response Time
Post-purge
PS Fault Delay (failed open/close)
Soft Lockout
TCO Limit Lockout
Verify Resistive Delay
Simulated Resistive Load Lockout
Hardware Error Lockout
15 Seconds
90 Seconds
3 Seconds
15 Seconds
1.5 Seconds (2 second. Maximum; 1 second minimum.)
15 Seconds
Retry after 2 Minutes
Retry after 5 Minutes
Indefinite (cycle power to restart)
Retry after 2 Minutes (repeats 5 times)
Indefinite (cycle power to restart)
Indefinite (self clears if fault clears for at least 15 seconds)
Specifications
Timing
Page 9