Gas Control & Thermal Well Testing & Replacement - Bradford White PDX Series Service Manual

Powered direct vent gas water heaters
Table of Contents

Advertisement

PDX Series
Gas Control Testing
See pages 27 & 28 for gas control
input & output testing.
Thermal Well Testing
If Control has gone into TCO lockout due to excessive
tank temperature (four flash, 3 second pause) reset
control by rotating knob of temperature control to the
minimum setting for at least 6 seconds before returning
to desired temperature setting.
Observe heater operation. If control
continues to lockout due to excessive
tank temperature, proceed to thermal
well testing to determine cause.
Thermal well testing
Position gas control power switch to
the "OFF" position and disconnect
thermal well harness from gas
control.
Using a multi-meter set to the
Ohms setting, determine the
resistance of thermal well sensor
(see caution photos 20 & 21)
Once the thermal well resistance values are known, the water
temperature must also be known to determine if the resistance
values are correct. See page 25 to obtain water temperature.
Are thermal well resistance values correct?
24
Using a multi-meter set to the ohms setting, insert one meter probe (see caution)
into center wire position of thermal well connector, insert the second probe (see
caution) into either of the outside wire positions (see photo 20).
Alternate the probe on the outside position to the opposite outside wire position
(see photo 21).
Y
Replace gas control
(see page 27)
PDX SERVICE PROCEDURE VI
Gas Control/Thermal Well Testing and
Disconnect thermal
well wire harness
20
CAUTION
DO NOT use standard multimeter probes for this test. Doing
so will damage connector. Use special pin type electronic
probes or small diameter wire pins inserted into connector.
N
Replace thermal well
(see page 27)
Replacement
21
Page 24