1.
About PROFIBUS-DP
1.1

Overview

PROFIBUS-DP
TM
is a communication protocol used to network industrial devices to eliminate labor intensive and
expensive point to point wiring schemes. Siemens originally developed PROFIBUS DP, but it is now supported by a
multitude of manufacturers and the protocol standard governed by the PROFIBUS Trade Organization (PTO).
The G3 Series PROFIBUS-DP
PROFIBUS Interface Center (PIC) according to the guidelines determined by the PROFIBUS Trade Organization (PTO).
The certification process ensures interoperability for all PROFIBUS-DP devices. This product supports PROFIBUS DP-V0
and DP-V1
PROFIBUS-DP
uses a 2-wire (plus shield) network and can have up to 126 nodes. The protocol can transfer a
TM
maximum of 244 bytes of data per node cycle with nine selectable communication (baud) rates of 9.6 Kbps, 19.2
Kbps, 45.45 Kbps, 93.75 Kbps, 187.5 Kbps, 500 Kbps, 1.5 Mbps, 3 Mbps, 6 Mbps and 12 Mbps. Maximum distance is
depended upon baud rate and cable media type. Refer to the section below for details.
More information about PROFIBUS can be obtained from the PROFIBUS web site
1.2
G3 PROFIBUS-DP
Features
Bus Topology
Baud Rates Supported
Duplicate address detection
Error Correction
Address Setting options
1.3

Cabling and Drop Line Lengths (as defined by PROFIBUS specification)

Maximum Cable Length
Baud
Rate
Range/
Segment
G3 Series PROFIBUS-DP
TM
product is designed to conform to the PROFIBUS standard EN50170 and is certified by
TM
Features
TM
Description
Linear bus, active bus termination on both ends. Stub lines permitted
9.6 Kbps, 19.2 Kbps, 45.45 Kbps, 93.75 Kbps, 187.5 Kbps, 500 Kbps,
Node address must match address in Master configuration software,
If error detected, sender is requested to repeat the message
Via Software (with Profibus-DP
9.6Kbps 19.2Kbps 93.75Kbps 187.5Kbps 500Kbps 1.5Mbps
1200M
1200M
1200M
TDG3PTTM1-11EN
Subject to change without notice
www.asco.com
Technical Manual
TM
only for <= 1.5Mbit/sec baud rates.
1.5Mbps, 3 Mbps, 6 Mbps and 12 Mbps
before node will enter the data exchange mode
TM
Class 2 Master), with standard Manual
Configuration Module (MCM), or graphic display
1000M
400M
200M
07/2020
www.PROFIBUS.com
12Mbps
100M
2-6