1.5.2

Planning the system with ICP-MAP0012 CAN splitter module

4
Wiring with a CAN splitter module and a MAP LSN gateway module
Wiring with two CAN splitter modules
Cable length
The cable length of the splitted external BDB depends on the number of added keypads and
of the cable diameter.
The maximum cable length is 500 m per BDB connector.
4
Bosch Sicherheitssysteme GmbH
When using a CAN splitter module to split the external BDB into two independent areas,
chose one of the following wiring possibilities:
ICP-MAP0012
ICP-MAP0012
When planning the system with one or more CAN splitter modules, ensure to use an
appropriate cable length and diameter in accordance with the necessary number of
keypads.