Download Print this page

Safe Disable Input Function - YASKAWA CIMR-AC4A0103TAA Quick Start Manual

Ac drive a1000

Advertisement

8

Safe Disable Input Function

Specifications
Inputs / Outputs
Operation Time
Failure Probability
Performance Level
Precautions
DANGER! Improper use of the Safe Disable function can result in serious injury or even death.
Make sure the whole system or machinery that the Safe Disable function is used in complies with safety requirements. When
implementing the Safe Disable function into the safety system of a machine, a thorough risk assessment for the whole system has to
be carried out to assure it complies with relevant safety norms (e.g., ISO13849, IEC61508, EN/IEC62061,...).
DANGER! When using a PM motor, even if the drive output is shut off by the Safe Disable function, a break down of two output
transistors can cause current to flow through the motor winding, resulting in a rotor movement for a maximum angle of 180 degree
(electrically). Make sure such a situation would have no effect on the safety of the application when using the Safe Disable function.
This is not a concern with induction motors.
DANGER! The Safe Disable function can switch off the drive output, but does not cut the drive power supply and cannot electrically
isolate the drive output from the input. Always shut off the drive power supply when performing maintenance or installations on the
drive input side as well as the drive output side.
DANGER! When using the Safe Disable inputs, make sure to remove the wire links between terminals H1, H2, and HC that were
installed prior to shipment. Failing to do so will keep the Safe Disable circuit from operating properly and can cause injury or even
death.
DANGER! All safety features (including Safe Disable) should be inspected daily and periodically. If the system is not operating
normally, there is a risk of serious personal injury.
DANGER! Only a qualified technician with a thorough understanding of the drive, the instruction manual, and safety standards should
be permitted to wire, inspect, and maintain the Safe Disable input.
NOTICE: From the moment terminal inputs H1 and H2 have opened, it takes up to 1 ms for drive output to shut off completely. The
sequence set up to trigger terminals H1 and H2 should make sure that both terminals remain open for at least 1 ms in order to properly
interrupt drive output.
NOTICE: The Safe Disable Monitor (output terminals DM+ and DM-) should not be used for any other purpose than to monitor the
Safe Disable status or to discover a malfunction in the Safe Disable inputs. The monitor output is not considered a safe output.
Using the Safe Disable Function
The Safe Disable inputs provide a stop function in compliance with "Safe Torque Off" as defined in the IEC61800-5-2.
Safe Disable inputs have been designed to meet the requirements of the ISO13849-1, Category 3 PLd, and IEC61508,
SIL2.
A Safe Disable Status Monitor for error detection in the safety circuit is also provided.
Safe Disable Circuit
The Safe Disable circuit consists of two independent input channels that can block the output transistors. In addition, it
provides a monitoring channel that indicates the status of those two input channels.
The input can either use the drive internal power supply or an external power supply. Use jumper S3 on the terminal
board to select between Sink or Source mode with either internal or external power supply.
A single photo coupler output is available to monitor the status of the Safe Disable terminals.
Terminal Functions on page 17
YASKAWA Europe TOEP C710606 96A - AC Drive A1000 IP54 Wallmount - Quick Start Guide
Two Safe Disable inputs and one EDM output according to ISO13849-1 Cat. 3 PLd,
IEC61508 SIL2.
Time from input open to drive output stop is less than 1 ms.
Demand Rate Low
PFD = 5.15E
Demand Rate High or
PFH = 1.2E
Continuous
The Safe Disable feature satisfies all requirements of performance level d (PLd) as defined
by ISO13849-1 (this includes DC from EDM).
for signal specifications when using this output.
-5
-9
8 Safe Disable Input Function
Refer to Control Circuit
EN 35