Standard and quick response concealed pendent sprinkler
Table of Contents

Advertisement

Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
5.

OPERATION

During fire conditions, when the temperature around the sprinkler approaches its operating temperature, the cover plate detaches,
releasing the deflector. Continued heating of the exposed sprinkler causes the heat-sensitive liquid in the glass bulb to expand,
causing the glass to shatter, releasing the pip cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes
the deflector, forming a uniform spray pattern over a specific area of coverage determined by the water supply pressure at the
sprinkler to extinguish or control the fire.
6.
INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
7.
AVAILABILITY
Viking Sprinklers are available through a network of domestic and international distributors. See The Viking Corporation web site
for the closest distributor contact The Viking Corporation.
8.
GUARANTEE
For details of warranty, refer to Viking's current list price schedule or contact Viking directly.
Instructions:
(1) Select a Sprinkler Base Part Number
(2) Add the suffix for the desired Finish
(3) Add the suffix for the desired Sprinkler Temperature Rating
(4) Order a cover plate (refer to Table 2)
Example:
24682AE = 200 °F (93 °C) Temperature Rated Sprinkler with a standard Brass finish.
Size
Sprinkler
Base Part
NPT
BSPT
Number
24682
1/2"
22962
--
1/2"
Accessories
Part number
Description
23143
Installation wrench
5
14417
Concealed cover plate installer tool (available since 2007)
14867
Large concealed cover plate installer tool (available since 2007)
01731A
Sprinkler cabinet; holds up to 6 sprinklers (available since 1971)
Footnotes
Where a dash (-) is shown in the Finish suffix designation, insert the desired Temperature Rating suffix. See example above.
1.
Based on NFPA 13, NFPA 13R, and NFPA 13D. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having
2.
Jurisdiction. Refer to specific installation standards.
UL Listed as corrosion resistant.
3.
The corrosion resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Chart. These tests cannot and
4.
do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compatible with or suitable for the proposed
environment. For automatic sprinklers, the ENT coating is applied to all exposed exterior surfaces, including the waterway.
Requires a 1/2" ratchet which is not available from Viking.
5.
FM Approved as a decorative finish.
6.
The installer tool is for push-on style cover plates only.
7.
The installation wrench is intended to be used for a maximum of 500 sprinkler installations at a maximum torque of 14 ft-lbs (19 Nm).
8.
Form No. F_092121
Rev 01
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
TABLE 1: ORDERING INFORMATION
1: Finishes
Description
Suffix
--
Brass
A
ENT
JN
3,4,6
5,8
April 2023

TECHNICAL DATA

Sprinkler
Nominal
1
Temperature
Rating
Classification
Ordinary
155 °F (68 °C)
Intermediate
175 °F (79 °C)
Intermediate
200 °F (93 °C)
7
7
STANDARD AND
QUICK RESPONSE
CONCEALED PENDENT
SPRINKLER VK4621 (K5.6)
2: Temperature Ratings
Bulb
Max. Ambient
Color
Ceiling Temperature
Red
100 °F (38 °C)
Yellow
150 °F (65 °C)
Green
150 °F (65 °C)
Page 2 of 8