11. Electronic function

11.1. Display board

11.1.1. AUTO indicator
This indicator illuminates when the air conditioner is in AUTO operation.
11.1.2. TIMER indicator
This indicator illuminates when TIMER is set ON/OFF.
11.1.3. PRE.-DEF. Indicator (For Cooling & Heating models only)
This indicator illuminates when the air conditioner starts defrosting automatically or when the warm air
control feature is activated in heating mode.
11.1.4. TEMPERATURE indicator
Usually it displays the temperature settings. When change the setting temperature, this indicator begins
to flash, and stops 20 seconds later.
It displays the room temperature when the air conditioner is in FAN only operation.
When the unit stops operation, it returns to original factory settings.
Displays the malfunction code or protection code.
11.1.5. OPERATION indicator
This indicator flashes after power is on and illuminates when the unit is in operation.
11.1.6. FREQUENCY indicator
This indicator appears only when the compressor is in operation and indicates the current operating
frequency.

11.2. Protection

11.2.1. 3 minutes delay at restart for compressor.
11.2.2. Temperature protection of compressor top, compressor stops when the temp. of top of
compressor is more than 115℃, compressor runs when the temp. of top of compressor is less than
100℃.
11.2.3. Voltage protection, unit stop when the voltage is more than 260V and less than 175V.
11.2.4. Inverter module Protection, Inverter module Protection itself has a protection function against
current, voltage and temperature.
11.2.5. Sensor protection at open circuit and breaking disconnection
11.2.6. Fan Speed is out of control. When Indoor Fan Speed is too high (higher than 2100RPM) or too
low (lower than 300RPM), the unit stops and LED displays failure information and can't return to
normal operation automatically.
11.2.7. Cross Zero signal error warning. If there is no Cross Zero signals in 4 minutes, the unit stops
and LED displays failure information and can't return to normal operation automatically.

11.3. Fan-only mode

Fan speed is high/mid/low/ Auto

11.4. Cooling mode

11.4.1. The 4-way valve is closed at cooling mode.
11.4.2. The action of the compressor and the outdoor fan:
Room temp. up
Room temp. down
22
Service manual
Condition
T=Indoor Temp.
T> Ts+1
T<Ts+1
T> Ts
T<Ts
Compressor
Outdoor fan
On
Off
On
Off
On
Off
On
Off