Toshiba RAS-M07G3DV-E Service Manual page 17

Air-conditioner multi-split type
Hide thumbs Also See for RAS-M07G3DV-E:
Table of Contents

Advertisement

In addition to the above exclusive tools, the following equipments are necessary as the general tools.
1. Pipe cutter
2. Reamer
3. Pipe bender
4. Level vial
5. Screwdriver (+, –)
Also prepare the following equipments for other installation method and run check.
1. Clamp meter
2. Thermometer
Recovery
• When removing refrigerant from a system, either for
servicing or decommissioning, it is recommended
good practice that all refrigerants are removed
safely.
• When transferring refrigerant into cylinders, ensure
that only appropriate refrigerant recovery cylinders
are employed.
• Ensure that the correct number of cylinders for
holding the total system charge are available.
• All cylinders to be used are designated for the
recovered refrigerant and labelled for that refrigerant
(i.e. special cylinders for the recovery of refrigerant).
• Cylinders shall be complete with pressure relief
valve and associated shut-off valves in good working
order.
• Empty recovery cylinders are evacuated and, if
possible, cooled before recovery occurs.
• The recovery equipment shall be in good working
order with a set of instructions concerning the
equipment that is at hand and shall be suitable for
the recovery of flammable refrigerants.
• In addition, a set of calibrated weighing scales shall
be available and in good working order.
• Hoses shall be complete with leak-free disconnect
couplings and in good condition.
• Before using recovery machine check that it is
satisfactory working order, has been properly
maintained and that any associated electrical
components are sealed to prevent ignition in the
event of a refrigerant release.
• Consult manufacturer if in doubt.
• The recovered refrigerant shall be returned to the
refrigerant supplier in the correct recovery cylinder,
and the relevant Waste Transfer Note arranged.
• Do not mix refrigerants in recovery units and
especially not in cylinders.
• If compressors or compressor oils are to be
removed, ensure that they have been evacuated to
an acceptable level to make certain that flammable
refrigerant does not remain within the lubricant.
• The evacuation process shall be carried out prior to
returning the compressor to the suppliers.
• Only electric heating to the compressor body shall
be employed to accelerate this process.
• When oil is drained from a system, it shall be carried
out safely.
General tools
6. Spanner or Monkey wrench
7. Hole core drill
8. Tape measure
9. Metal saw
3. Insulation resistance tester (Megger)
4. Electroscope
Decommissioning
• Before carrying out this procedure, it is essential that
the technician is completely familiar with the
equipment and all its details. Only a qualified installer
(*1) or qualified service person (*1) is allowed to do
this work.
• It is recommended good practice that all refrigerants
are recovered safely.
• Prior to the task being carried out, an oil and
refrigerant sample shall be taken in case analysis is
required prior to re-use of reclaimed refrigerant.
• It is essential that electrical power is available before
the task is commenced.
a) Become familiar with the equipment and its
operation.
b) Isolate system electrically.
c) Before attempting the procedure ensure that:
• mechanical handling equipment is available, if
required, for handling refrigerant cylinders;
• all personal protective equipment is available and
being used correctly;
• the recovery process is supervised at all times by a
competent person;
• recovery equipment and cylinders conform to the
appropriate standards.
d) Pump down refrigerant system, if possible.
e) If a vacuum is not possible, make a manifold so that
refrigerant can be removed from the various parts of
the system.
f) Make sure that cylinder is situated on the scales
before recovery takes place.
g) Start the recovery machine and operate in
accordance with manufacturers instructions.
h) Do not overfill cylinders (No more than 80% volume
liquid change).
i) Do not exceed the maximum working pressure of
the cylinder, even temporarily.
j) When the cylinders have been filled correctly and
the process complete, make sure that the cylinders
and the equipment are removed from site promptly
and all isolation valves on the equipment are closed
off.
k) Recovered refrigerant shall not be changed into
another refrigerant system unless it has been
cleaned and checked.
– 16 –

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents