Omron SYSMAC C200H CPU01-E Installation Manual page 93

Table of Contents

Advertisement

Specifications
Triac Output Unit C200H-OA122-E
Circuit Configuration
Note When the fuse blows, the F indicator lights and bit 08 turns ON. Bits 08 through 15 cannot be used as work
bits.
Terminal Connections
Downloaded from
Elcodis.com
electronic components distributor
All manuals and user guides at all-guides.com
Max. Switching Capacity
Max. Inrush Current
Min. Switching Capacity
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
No. of Circuits
Internal Current Consumption
Fuse Rating
Power for External Supply
Weight
Dimensions
Output indicator
Internal
circuit
Fuse: 5 A 125 V (5.2-dia.x20) GGS (Nagasawa)
120 VAC max.
(1.2 A max. 4 A/Unit)
1.2 A 120 VAC, 50/60 Hz (4 A/Unit)
15 A (pulse width: 100 ms)
30 A (pulse width: 10 ms)
100 mA 10 VAC/50 mA 24 VAC/10 mA 100 VAC
min.
1.5 mA (120 VAC) max.
1.5 VAC max. (50 to 1,200 mA)/ 5 VAC max. (10 to
50 mA)
1 ms max.
1/2 of load frequency+1 ms or less.
1 (8 points/common)
180 mA 5 VDC max.
5 A 125 V (5.2-dia.x20)
N/A
300 g max.
E-shape
OUT
L
OUT
L
Fuse
COM
120 VAC max.
Fuse blowout
detection circuit
F indicator
0
L
A0
1
A1
L
2
A2
L
3
A3
L
4
A4
L
5
A5
L
6
A6
L
7
A7
L
A8
COM
A9
NC
Appendix B
79

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sysmac c200h cpu03-eSysmac c200h cpu11-e

Table of Contents