Omron SYSMAC C200H CPU01-E Installation Manual page 109

Table of Contents

Advertisement

Specifications
Transistor Output Unit C200H-OD411
Circuit Configuration
Note When the fuse blows F LED lights and bit 08 turns ON. Bits 08 through 15 cannot be used as work bits.
Terminal Connections
Note Be sure to supply power to A9; otherwise current will leak through the load while the output is OFF.
Downloaded from
Elcodis.com
electronic components distributor
All manuals and user guides at all-guides.com
Max. switching capacity
Min. switching capacity
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
No. of Circuits
Internal Current Consumption
Fuse Rating
Power for External Supply
Weight
Dimensions
Output LED indicator
Internal
circuit
Fuse blowout
detection circuit
F LED
12 to 48 VDC
(1 A max., 3 A/Unit)
12 to 48 VDC 1 A (3 A/Unit)
None
0.1 mA max.
1.4 V max.
0.2 ms max.
0.3 ms max.
1 (8 points/common)
140 mA 5 VDC max.
5 A 125 V (5.2-dia.x20)
30 mA 12 to 48 VDC max.
250 g max.
A-shape
OUT
L
V
OUT
L
Fuse
COM
12 to
48 VDC
0
L
A0
1
A1
L
2
A2
L
3
A3
L
4
A4
L
5
A5
L
6
A6
L
7
A7
L
A8
COM (0 V)
12 to 48 VDC
A9
Appendix B
95

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sysmac c200h cpu03-eSysmac c200h cpu11-e

Table of Contents