Lift Input Starter; Storage - Trane VFDB Installation, Operation And Maintenance Manual

Remote-mounted medium voltage air-cooled adaptive frequency drive with tracer adaptiview control
Table of Contents

Advertisement

Figure 25. Overhead lifting (isolation transformer
cabinet)
45° maximum
Minimum height of
1.5 m (5 ft)

Lift Input Starter

The lifting angles hold the starting/junction cabinet together to
prevent separation and damage while riggers move the drive
to the final installation area.
The lifting angles are shipped with the starting/junction cabinet
and must be secured before lifting the cabinet.
1. Remove the lifting angles from the skid.
2. Remove the attachment hardware that is pre-installed in
the mounting holes in the top plate of the cabinet before
shipment.
3. Align and secure the lifting angles in four places as shown
in below figure.
4. Re-install the hardware (M12 x 2) and the pre-installed
attachment hardware (M6) in the mounting holes (to seal
the holes) on the top of the drive.
VFDB-SVX001C-EN
Steel cable
U-rings
Lifting provision
Figure 26. Overhead lifting (starting/junction cabinet)

Storage

NOTICE
Equipment Damage!
Failure to follow storage recommendations could result
in equipment-only damage. Read this section carefully
and follow all recommendations for drive storage.
If the storage of the equipment is longer than one year, it is
recommended to power up once a year.
If equipment containing electrolytic capacitors (like power
supplies, power cells, etc.) is stored (unpowered) under
normal storage temperatures and conditions, it can be kept up
to 15 years.
Storage the drive in a dry, clean, and cool area.
The storage temperature must be maintained between -
40...+70 °C (-40...+158 °F). This temperature rating applies
only to the drive, it does not include the UPS (Uninterruptible
Power Supply). If the storage temperature fluctuates
significantly or if the relative humidity exceeds 95%, use
heating and moisture protection devices to prevent
condensation.
Store the drive in a conditioned building with adequate air
circulation. Do not store the drive outdoors.
Pre-Installation
Lifting Angle pair
M12 bolt
Washer
45°
Minimum height of
maximum
1.5 m (5 ft)
35