Installation
Figure 68. Low voltage wiring — D cabinet
Figure 69. Main control panel low voltage wiring
Table 9.
Recommended wire lengths
Wire Size
2
AWG
mm
22
0.33
20
0.50
18
0.75
16
1.30
14
2.00
Note: The total resistance of these low voltage wires must not exceed 2.5
Ω/conductor. Any resistance greater than 2.5 Ω may cause the
control to malfunction due to an excessive voltage drop.
46
Maximum recommended wire
length from unit controller to
sensor
Meters
Feet
0–46
0–150
47–73
151–240
74–117
241–385
118–185
386–610
186–296
611–970

Controls using DC Analog Input/Outputs

(Standard Low Voltage Multi conductor
Wire)
Before installing any connecting wiring between the unit
and components utilizing a DC analog input\output signal,
refer to the Dimensions and Weights chapter for the
electrical access locations provided on the unit.
Table 10, p. 47
lists the conductor sizing guidelines that
must be followed when interconnecting the DC binary
output devices and the system components utilizing a
DC analog input/output signal to the unit.