1.3 Installation

The device is only allowed to be installed and operated within the permissible
temperature range. Please ensure an adequate ventilation and avoid all direct
contact between the device and hot or aggressive gases and liquids.
Before installation or maintenance, the unit must be disconnected from all voltage-
sources. Further it must be ensured that no danger can arise by touching the
disconnected voltage-sources.
Devices which are supplied by AC-voltages, must be connected exclusively by
switches, respectively circuit-breakers with the low voltage network. The switch or
circuit-breaker must be placed as near as possible to the device and further indicated
as separator.
Incoming as well as outgoing wires and wires for extra low voltages (ELV) must be
separated from dangerous electrical cables (SELV circuits) by using a double resp.
increased isolation.
All selected wires and isolations must be conform to the provided voltage- and
temperature-ranges. Further all country- and application-specific standards, which
are relevant for structure, form and quality of the wires, must be ensured.
Indications about the permissible wire cross-sections for wiring are described in the
Technical Specifications (see chapter 8).
Before first start-up it must be ensured that all connections and wires are firmly
seated and secured in the screw terminals. All (inclusively unused) terminals must be
fastened by turning the relevant screws clockwise up to the stop.
Overvoltages at the connections must be limited to values in accordance to the
overvoltage category II.
For placement, wiring, environmental conditions as well as shielding and
earthing/grounding of the supply lines the general standards of industrial automation
industry and the specific shielding instructions of the manufacturer are valid. Please
find all respective hints and rules on www.hohner-elektrotechnik.de.

1.4 Cleaning, Maintenance and Service Notes

To clean the front of the unit please use only a slightly damp (not wet!), soft cloth.
For the rear no cleaning is necessary. For an unscheduled, individual cleaning of the
rear the maintenance staff or assembler is self-responsible.