5.4. Setting the A/B divider (for all other modes)
The division ratio for the A/B pulses is set at the DIL switches DIL5 and DIL6. The
switch positions use a binary code like shown in the subsequent list. (DIL1/6 = OFF,
DIL1/7 = X).
DIL5
(Lefts 8-pole)
1
2
3
4
ON
OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF
OFF ON OFF OFF OFF OFF OFF OFF OFF OFF OFF
ON
ON OFF OFF OFF OFF OFF OFF OFF OFF OFF
OFF OFF ON OFF OFF OFF OFF OFF OFF OFF OFF
ON
OFF ON OFF OFF OFF OFF OFF OFF OFF OFF
OFF ON ON OFF OFF OFF OFF OFF OFF OFF OFF
ON
ON ON OFF OFF OFF OFF OFF OFF OFF OFF
OFF OFF OFF OFF OFF OFF OFF OFF OFF ON OFF
OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF ON
ON
ON ON ON ON ON ON ON ON ON ON
Example: Input A/B 90°, output A/B 90 ° with A/B division 1:6 (setting DIL6, 5: OFF
ON OFF
Example: Input A/B 90°, output A/B 90 ° with A/B division 1:3 (setting DIL6, 5: OFF
ON OFF
Example: Input A/B 90°, output A/B 90 ° with A/B division 1:3 (setting DIL6, 5: OFF
ON OFF
It210_01a_oi_e.docx / Jan-20
www.hohner-elektrotechnik.de
(Left 3-pole)
5
6
7
8
1
Divider [A/B]
DIL6
Comment
2
3
Binary value
Division =>
1 : Binary value +1
value 1 => 1 : 2
value 2 => 1 : 3
value 3 => 1 : 4
value 4 => 1 : 5
value 5 => 1 : 6
value 6 => 1 : 7
value 7 => 1 : 8
...etc.
1 : 513
1 : 1025
1 : 2048
Page 12 / 21
13