Operation Of The Potential-Free Failure/Alarm Contact; How To Change Operating Parameters - Setup Menu; Electronically Level-Controlled Bekomat Condensate Drain - Beko DRYPOINT RA CT Series Instructions For Installation And Operation Manual

Compressed air refrigeration dryer
Table of Contents

Advertisement

Technical description

11.12.6 Operation of the potential-free failure/alarm contact

The DMC51 is equipped with a 12Vdc signal (max 15 mA) to indicate service warning or alarm conditions.
11.12.7 How to change operating parameters – SETUP menu
The setup menu can be used to change the dryer's operating parameters.
Only qualified personnel must be allowed to access to the setup menu. The manufacturer is
not responsible for malfunctioning or failure due to modification to the operating parameters.
With dryer ON simultaneously press buttons
Access to the menu is confirmed by message
Set
Keep
pressed to display the value of the selected parameter and use arrows
the value. Release the button
Press
+
automatically).
ID
HdS - High DewPoint Setting : service warning threshold for
a high DewPoint (the service warning disappears when the
temperature drop 0.5°C / 1°F below set point)
Hdd - High DewPoint Delay : high DewPoint service
warning enable delay
SrV - Service Setting : setting of service warning timer.
0.0 = service warning timer disabled.
SCL - Scale: display scale of temperatures.
ESS – Energy Saving Set: selection if dryer run in energy
saving cycle.
YES = Energy saving mode is active (cycling mode).
nO = Energy saving mode is not active (Hot Gas by-pass
sytem)

11.13 Electronically level-controlled BEKOMAT condensate drain

The electronically level-controlled BEKOMAT condensate drain boasts a special condensate management which
ensures that condensate is discharged safely and without an unnecessary loss of compressed air. This drain has a
condensate collection container in which a capacitive sensor continuously monitors the liquid level. As soon as the
switching level is reached, the capacitive sensor transmits a signal to the electronic control and a membrane solenoid
valve opens to discharge the condensate. The BEKOMAT closes before compressed air emerges.
Note!
These BEKOMAT condensate drains were designed in particular for the operation in a DRYPOINT RA
CT refrigeration dryer. The installation in other compressed-air processing systems or the replacement
with another drain brand can lead to malfunction. The maximum operating pressure (see name plate)
must not be exceeded!
Ensure that the upstream valve is open when the dryer starts operation.
To obtain detailed information regarding drain functions, troubleshooting, maintenance and
spare parts, please read the installation and operating instructions of the BEKOMAT condensate
drain.
26
Dryer is switched on, no service warning and no alarm (active and not yet reset) are
indicated.
Dryer is off or a service warning or an alarm (active and not yet reset) is indicated.
Set
to confirm the value and skip to following parameter.
to exit setup menu (if no button is pressed after 30 seconds the menu is exited
Description
Set
+
for at least 5 seconds to enter the setup menu.
on the display (first parameter of menu).
0.0...25.0 °C
32 ... 77 °F
00 ... 20
0.0 ... 9.0
YES...nO
and
Limits
Resolution
0.5 °C
or
or
1 °F
1 min
minutes
0.1
(x 1000)
(x1000) hours
hours
°C ... °F
-
-
DRYPOINT® RA CT 200-500 NA 3PH
to change
Standard
setup
20
or
68
15
8.0
°C or °F
YES