This material is protected by copyright laws. It may not be reproduced, distributed, or altered in any fashion by any entity (either internal or external to Yaskawa) except in accordance with applicable agreements, contracts or licensing, without the express written consent of Yaskawa and the business management owner of the material.
Tel.: +49 6196 569 500 (hotline) Email: support@yaskawa.eu.com 1.2 About this manual Objective and contents This manual describes the power supplys for the System 300 from Yaskawa. It contains a description of the construction, usage and technical data. Product Order number...
System 300S General Safety information 1.3 Safety information Applications conforming The system is constructed and produced for: with specifications communication and process control general control and automation tasks industrial applications operation within the environmental conditions specified in the technical data...
System 300S Assembly and installation guidelines Safety information for users Assembly and installation guidelines 2.1 Safety information for users Handling of electrostatic The modules make use of highly integrated components in MOS-Technology. These com- sensitive modules ponents are extremely sensitive to over-voltages that can occur during electrostatic dis- charges.
System 300S Assembly and installation guidelines Installation dimensions 2.2 Installation dimensions Dimensions Basic 1tier width (WxHxD) in mm: 40 x 125 x 120 enclosure 1tier width (WxHxD) in mm: 80 x 125 x 120 1tier width (WxHxD) in mm: 120 x 125 x 120...
Measures in mm Bus connector For the communication between the modules the System 300S uses a backplane bus connector. Backplane bus connectors are included in the delivering of the peripheral modules and are clipped at the module from the backside before installing it to the profile rail.
Page 10
System 300S Assembly and installation guidelines Installation at the profile rail Assembly possibilities Please regard the allowed environment temperatures: horizontal assembly: from 0 to 60°C vertical assembly: from 0 to 40°C The horizontal structure always starts at the left side with the power supply and the CPU, then you plug-in the peripheral modules beside to the right.
System 300S Assembly and installation guidelines Cabling CAUTION! – Before installing or overhauling the power supplies must be discon- nected from voltage (pull the plug or remove the fuse)! – Installation and modifications only by properly trained personnel! 2.4 Cabling Overview For the cabling of power supplies gray connectors with CageClamp technology are used.
The components of Yaskawa are developed for the deployment in industrial environments and meets high demands on the EMC. Nevertheless you should project an EMC planning before installing the components and take conceivable interference causes into account.
Page 13
System 300S Assembly and installation guidelines Installation guidelines Proof the correct fixing of the lead isolation. – Data lines must be shielded. – Analog lines must be shielded. When transmitting signals with small amplitudes the one sided laying of the isolation may be favourable.
System 300S Assembly and installation guidelines General data 2.6 General data Conformity and approval Conformity 2014/35/EU Low-voltage directive 2014/30/EU EMC directive Approval Refer to Technical data others RoHS 2011/65/EU Restriction of the use of certain hazardous substances in electrical and electronic equipment...
System 300S Assembly and installation guidelines General data > Use in difficult operating conditions Mounting conditions Mounting place In the control cabinet Mounting position Horizontal and vertical Standard Comment Emitted interference EN 61000-6-4 Class A (Industrial area) Noise immunity EN 61000-6-2...
System 300S Power supply PS 307 Safety Information Power supply PS 307 3.1 Safety Information Application fields The power supplies are constructed and manufactured for: DC 24V supply of System 300 components. Installation together with other System 300 components on one panel.
System 300S Power supply PS 307 System overview 3.2 System overview Power supplies The System 300 power supplies presented here have an adjustable input voltage of AC 120/230V and an output voltage of DC 24V. Depending on the module, the voltage is adjusted via a 120 / 230V switch or automatically continuously from AC 100 ...
System 300S Power supply PS 307 PS 307-1BA00 3.3 PS 307-1BA00 Properties Output current 2.5A Output voltage DC 24V Connection to single-phase AC mains Wide-range input AC 100...240V without manual switch Protection against short circuits, overloads and vacancy Useable together with System 300 on profile rail...
Page 19
System 300S Power supply PS 307 PS 307-1BA00 Structure Status LED ON/OFF switch The following components are beneath a flap: AC IN 100 ... 240V DC OUT 24V, 2.5A CAUTION! – The power supplies must be released before installation and repair tasks, i.e.
Page 20
System 300S Power supply PS 307 PS 307-1BA00 Output DC 24V, 2.5A Here you may connect System 300 modules to two sockets, that need a external DC 24V voltage. Both outputs are protected against short circuits and have each an output voltage of DC 24V at a total current of max.
System 300S Power supply PS 307 PS 307-1BA00 > Technical data 3.3.1 Technical data Order no. 307-1BA00 Type PS 307 SPEED-Bus Technical data power supply Input voltage (rated value) AC 100...240 V Input voltage (permitted range) AC 100...240 V Mains frequency (rated value) 50...60 Hz...
Page 22
System 300S Power supply PS 307 PS 307-1BA00 > Technical data Order no. 307-1BA00 Weight including accessories Gross weight Environmental conditions Operating temperature 0 °C to 60 °C Storage temperature -25 °C to 70 °C Certifications UL certification KC certification...
System 300S Power supply PS 307 PS 307-1EA00 3.4 PS 307-1EA00 Properties Output current 5A Output voltage DC 24V Connection to single-phase AC mains AC 120/230V, 60/50Hz (switchable) Protection against short circuits, overloads and vacancy Useable together with System 300 on profile rail...
Page 24
System 300S Power supply PS 307 PS 307-1EA00 CAUTION! – The power supplies must be released before installation and repair tasks, i.e. before handling with the power supply or with the cabling you must disconnect current/voltage (pull plug, at fixed connection switch off the concerning fuse)! –...
Page 25
System 300S Power supply PS 307 PS 307-1EA00 Mains voltage selector switch On delivery the power supply is adjusted to AC 230V input voltage. At the front side of the power supply there is a mains voltage selector switch to switch input voltage to AC 120V.
Page 26
System 300S Power supply PS 307 PS 307-1EA00 CAUTION! – Before installing or overhauling single components res. the whole system, the power supplies must be disconnected from voltage (pull the plug or remove the fuse)! – Installation and modifications only by properly trained personnel! –...
System 300S Power supply PS 307 PS 307-1EA00 > Technical data 3.4.1 Technical data Order no. 307-1EA00 Type PS 307 SPEED-Bus Technical data power supply Input voltage (rated value) AC 120/230 V Input voltage (permitted range) AC 90...132/180...264 V Mains frequency (rated value) 50...60 Hz...
Page 28
System 300S Power supply PS 307 PS 307-1EA00 > Technical data Order no. 307-1EA00 Weight including accessories Gross weight Environmental conditions Operating temperature 0 °C to 60 °C Storage temperature -25 °C to 70 °C Certifications UL certification KC certification...
System 300S Power supply PS 307 PS 307-1KA00 3.5 PS 307-1KA00 Properties Output current 10A Output voltage DC 24V Connection to single-phase AC mains AC 120/230V, 60/50Hz (switchable) Protection against short circuits, overloads and vacancy Useable together with System 300 on profile rail...
Page 30
System 300S Power supply PS 307 PS 307-1KA00 CAUTION! – The power supplies must be released before installation and repair tasks, i.e. before handling with the power supply or with the cabling you must disconnect current/voltage (pull plug, at fixed connection switch off the concerning fuse)! –...
Page 31
System 300S Power supply PS 307 PS 307-1KA00 Mains voltage selector switch On delivery the power supply is adjusted to AC 230V input voltage. At the front side of the power supply there is a mains voltage selector switch to switch input voltage to AC 120V.
Page 32
System 300S Power supply PS 307 PS 307-1KA00 CAUTION! – Before installing or overhauling single components res. the whole system, the power supplies must be disconnected from voltage (pull the plug or remove the fuse)! – Installation and modifications only by properly trained personnel! –...
System 300S Power supply PS 307 PS 307-1KA00 > Technical data 3.5.1 Technical data Order no. 307-1KA00 Type PS 307 SPEED-Bus Technical data power supply Input voltage (rated value) AC 120/230 V Input voltage (permitted range) AC 90...132/180...264 V Mains frequency (rated value) 50...60 Hz...
Page 34
System 300S Power supply PS 307 PS 307-1KA00 > Technical data Order no. 307-1KA00 Weight including accessories Gross weight Environmental conditions Operating temperature 0 °C to 60 °C Storage temperature -25 °C to 70 °C Certifications UL certification KC certification...