VIPA System 300 General About this manual VIPA GmbH, Ohmstraße 4, 91074 Herzogenaurach, Germany Telefax: +49 9132 744-1204 EMail: documentation@vipa.de Technical support Contact your local VIPA Customer Service Organization representative if you encounter problems with the product or have questions regarding the product. If you are unable to locate a customer service centre, contact VIPA as follows: VIPA GmbH, Ohmstraße 4, 91074 Herzogenaurach, Germany Tel.: +49 9132 744-1150 (Hotline)
VIPA System 300 General Safety information Supplementary information and useful tips. 1.3 Safety information Applications conforming The system is constructed and produced for: with specifications communication and process control general control and automation tasks industrial applications operation within the environmental conditions specified in the technical data installation into a cubicle DANGER! This device is not certified for applications in...
VIPA System 300 Assembly and installation guidelines Safety information for users Assembly and installation guidelines 2.1 Safety information for users Handling of electrostatic VIPA modules make use of highly integrated components in MOS-Technology. These sensitive modules components are extremely sensitive to over-voltages that can occur during electrostatic discharges.
VIPA System 300 Assembly and installation guidelines Installation dimensions 2.2 Installation dimensions Dimensions Basic 1tier width (WxHxD) in mm: 40 x 125 x 120 enclosure 1tier width (WxHxD) in mm: 80 x 125 x 120 1tier width (WxHxD) in mm: 120 x 125 x 120 Dimensions Installation dimensions HB130 | PS | 307-1xA00 | en | 18-01...
VIPA System 300 Assembly and installation guidelines Installation at the profile rail 2.3 Installation at the profile rail General The single modules are directly installed on a profile rail and connected via the backplane bus connector. Before installing the modules you have to clip the backplane bus con- nector to the module from the backside.
Page 10
VIPA System 300 Assembly and installation guidelines Installation at the profile rail Assembly possibilities Please regard the allowed environment temperatures: horizontal assembly: from 0 to 60°C vertical assembly: from 0 to 40°C The horizontal structure always starts at the left side with the power supply and the CPU, then you plug-in the peripheral modules beside to the right.
VIPA System 300 Assembly and installation guidelines Cabling CAUTION! – Before installing or overhauling the power supplies must be discon- nected from voltage (pull the plug or remove the fuse)! – Installation and modifications only by properly trained personnel! 2.4 Cabling Overview For the cabling of power supplies gray connectors with CageClamp technology are used.
Page 12
VIPA System 300 Assembly and installation guidelines Cabling CageClamp technology For the cabling of power supplys a green plug with CageClamp technology is deployed. (gray) AC IN 100 ... 240V DC OUT 24V The picture on the left side shows the cabling step by step from top view. Here wires with a cross-section of 0.08mm to 2.5mm may be connected.
VIPA System 300 Assembly and installation guidelines Installation guidelines 2.5 Installation guidelines General The installation guidelines contain information about the interference free deployment of a PLC system. There is the description of the ways, interference may occur in your PLC, how you can make sure the electromagnetic compatibility (EMC), and how you manage the isolation.
Page 14
VIPA System 300 Assembly and installation guidelines Installation guidelines Proof the correct fixing of the lead isolation. – Data lines must be laid isolated. – Analog lines must be laid isolated. When transmitting signals with small ampli- tudes the one sided laying of the isolation may be favourable. –...
VIPA System 300 Assembly and installation guidelines General data 2.6 General data Conformity and approval Conformity 2014/35/EU Low-voltage directive 2014/30/EU EMC directive Approval Refer to Technical data others RoHS 2011/65/EU Restriction of the use of certain hazardous substances in electrical and electronic equipment Protection of persons and device protection Type of protection IP20...
Page 16
VIPA System 300 Assembly and installation guidelines General data Mounting conditions Mounting place In the control cabinet Mounting position Horizontal and vertical Standard Comment Emitted interference EN 61000-6-4 Class A (Industrial area) Noise immunity EN 61000-6-2 Industrial area zone B EN 61000-4-2 8kV at air discharge (degree of severity 3), 4kV at contact discharge (degree of severity 2)
VIPA System 300 Power supply PS 307 Safety Information Power supply PS 307 3.1 Safety Information Application fields The power supplies are constructed and manufactured for: DC 24V supply of System 300 components. Installation together with other System 300 components on one panel. Installation in a cubicle with air condition.
VIPA System 300 Power supply PS 307 System overview 3.2 System overview Power supplies The System 300 power supplies presented here have an adjustable input voltage of AC 120/230V and an output voltage of DC 24V. Depending on the module, the voltage is adjusted via a 120 / 230V switch or automatically continuously from AC 100 ...
VIPA System 300 Power supply PS 307 PS 307-1BA00 3.3 PS 307-1BA00 Properties Output current 2.5A Output voltage DC 24V Connection to single-phase AC mains Wide-range input AC 100...240V without manual switch Protection against short circuits, overloads and vacancy Useable together with System 300 on profile rail...
Page 20
VIPA System 300 Power supply PS 307 PS 307-1BA00 Structure Status LED ON/OFF switch The following components are beneath a flap: AC IN 100 ... 240V DC OUT 24V, 2.5A CAUTION! – The power supplies must be released before installation and repair tasks, i.e.
Page 21
VIPA System 300 Power supply PS 307 PS 307-1BA00 Output DC 24V, 2.5A Here you may connect System 300 modules to two sockets, that need a external DC 24V voltage. Both outputs are protected against short circuits and have each an output voltage of DC 24V at a total current of max.
VIPA System 300 Power supply PS 307 PS 307-1BA00 > Technical data 3.3.1 Technical data Order no. 307-1BA00 Type PS 307 SPEED-Bus Technical data power supply Input voltage (rated value) AC 100...240 V Input voltage (permitted range) AC 100...240 V Mains frequency (rated value) 50...60 Hz...
Page 23
VIPA System 300 Power supply PS 307 PS 307-1BA00 > Technical data Order no. 307-1BA00 Weight including accessories Gross weight Environmental conditions Operating temperature 0 °C to 60 °C Storage temperature -25 °C to 70 °C Certifications UL certification KC certification...
VIPA System 300 Power supply PS 307 PS 307-1EA00 3.4 PS 307-1EA00 Properties Output current 5A Output voltage DC 24V Connection to single-phase AC mains AC 120/230V, 60/50Hz (switchable) Protection against short circuits, overloads and vacancy Useable together with System 300 on profile rail Safety isolation to EN 60950 May be used as load power supply Order data...
Page 25
VIPA System 300 Power supply PS 307 PS 307-1EA00 CAUTION! – The power supplies must be released before installation and repair tasks, i.e. before handling with the power supply or with the cabling you must disconnect current/voltage (pull plug, at fixed connection switch off the concerning fuse)! –...
Page 26
VIPA System 300 Power supply PS 307 PS 307-1EA00 Mains voltage selector switch On delivery the power supply is adjusted to AC 230V input voltage. At the front side of the power supply there is a mains voltage selector switch to switch input voltage to AC 120V. For this remove the transparent plastic cover by means of a screwdriver.
Page 27
VIPA System 300 Power supply PS 307 PS 307-1EA00 CAUTION! – Before installing or overhauling single components res. the whole system, the power supplies must be disconnected from voltage (pull the plug or remove the fuse)! – Installation and modifications only by properly trained personnel! –...
VIPA System 300 Power supply PS 307 PS 307-1EA00 > Technical data 3.4.1 Technical data Order no. 307-1EA00 Type PS 307 SPEED-Bus Technical data power supply Input voltage (rated value) AC 120/230 V Input voltage (permitted range) AC 90...132/180...264 V Mains frequency (rated value) 50...60 Hz Mains frequency (permitted range)
Page 29
VIPA System 300 Power supply PS 307 PS 307-1EA00 > Technical data Order no. 307-1EA00 Weight including accessories Gross weight Environmental conditions Operating temperature 0 °C to 60 °C Storage temperature -25 °C to 70 °C Certifications UL certification KC certification HB130 | PS | 307-1xA00 | en | 18-01...
VIPA System 300 Power supply PS 307 PS 307-1KA00 3.5 PS 307-1KA00 Properties Output current 10A Output voltage DC 24V Connection to single-phase AC mains AC 120/230V, 60/50Hz (switchable) Protection against short circuits, overloads and vacancy Useable together with System 300 on profile rail Safety isolation to EN 60950 May be used as load power supply Order data...
Page 31
VIPA System 300 Power supply PS 307 PS 307-1KA00 CAUTION! – The power supplies must be released before installation and repair tasks, i.e. before handling with the power supply or with the cabling you must disconnect current/voltage (pull plug, at fixed connection switch off the concerning fuse)! –...
Page 32
VIPA System 300 Power supply PS 307 PS 307-1KA00 Mains voltage selector switch On delivery the power supply is adjusted to AC 230V input voltage. At the front side of the power supply there is a mains voltage selector switch to switch input voltage to AC 120V. For this remove the transparent plastic cover by means of a screwdriver.
Page 33
VIPA System 300 Power supply PS 307 PS 307-1KA00 CAUTION! – Before installing or overhauling single components res. the whole system, the power supplies must be disconnected from voltage (pull the plug or remove the fuse)! – Installation and modifications only by properly trained personnel! –...
VIPA System 300 Power supply PS 307 PS 307-1KA00 > Technical data 3.5.1 Technical data Order no. 307-1KA00 Type PS 307 SPEED-Bus Technical data power supply Input voltage (rated value) AC 120/230 V Input voltage (permitted range) AC 90...132/180...264 V Mains frequency (rated value) 50...60 Hz Mains frequency (permitted range)
Page 35
VIPA System 300 Power supply PS 307 PS 307-1KA00 > Technical data Order no. 307-1KA00 Weight including accessories Gross weight Environmental conditions Operating temperature 0 °C to 60 °C Storage temperature -25 °C to 70 °C Certifications UL certification KC certification HB130 | PS | 307-1xA00 | en | 18-01...