Maintenance Checklist - Roberts Gorden GordonRay BH-60 Installation, Operation & Service Manual

Economical unitary infrared heater
Table of Contents

Advertisement

BH-S
I
, O
ERIES
NSTALLATION
PERATION AND
overall heater condition should be thoroughly
inspected.
NOTE: Gas flow and burner ignition are among the
first things that should be throughly inspected.
Please see Page 52, Section 11.5 for suggested
items to inspect.

11.5 Maintenance Checklist

Installation Code and Annual Inspections:
All installation and service of ROBERTS GORDON
equipment must be performed by a contractor
qualified in the installation and service of equipment
sold and supplied by Roberts-Gordon LLC and
The Vicinity of the Heater
Vehicles and Other
Objects
Reflector
Vent Pipe
Outside Air Inlet
Tubes
Gas Line
Burner Observation
Window
52 of 63
S
M
ERVICE
ANUAL
Do not store or use flammable objects, liquids or vapors near the heater.
Immediately remove these items if they are present.
See Page 5, Section 3.
Maintain the clearances to combustibles.
Do not hang anything from, or place anything on, the heater.
Make sure nothing is lodged underneath the reflector, in between the tubes or
in the decorative or protective grilles (included with select models).
Immediately remove objects in violation of the clearances to combustibles.
See Page 5, Section 3.
Support reflector with reflector hanger and support strap.
Reflector must not touch tube.
Make sure there is no dirt, sagging, cracking or distortion.
Do not operate if there is sagging, cracking or distortion.
Make sure reflectors are correctly overlapped. See Page 25, Section 6.5.1.
Clean outside surface with a damp cloth.
Venting must be intact. Using a flashlight, look for obstructions, cracks on the
pipe, gaps in the sealed areas or corrosion.
The area must be free of dirt and dust.
Remove any carbon deposits or scale using a wire brush.
See Page 37 , Section 8.
Inlet must be intact. Look for obstructions, cracks on the pipe, gaps in the
sealed areas or corrosion.
The area must be free of dirt and dust. Clean and reinstall as required.
Make sure there are no cracks.
Make sure tubes are connected and suspended securely.
See Page 16, Section 6.
Make sure there is no sagging, bending or distortion.
Clean or replace as required.
Check for gas leaks. See Page 45, Section 9.
Make sure it is clean and free of cracks or holes.
Clean and replace as required.
conform to all requirements set forth in the
ROBERTS GORDON
governmental authorities pertaining to the
installation, service, operation and labeling of the
equipment.
To help facilitate optimum performance and safety,
Roberts-Gordon LLC recommends that a qualified
contractor conduct, at a minimum, annual
inspections of your ROBERTS GORDON
and perform service where necessary, using only
®
replacement parts sold and supplied by Roberts-
Gordon LLC.
manuals and all applicable
®
equipment
®

Hide quick links: