Transient Voltage (Impulse)

Measurement Type............................................. Waveshape sampling, not peak detect
Full Scale ............................................................ 8000 V pk
Sample Resolution.............................................. 200 nS
Measurement Uncertainty................................... ± 5 % reading ± 20 V (test parameters: 1000 V dc, 1000 V rms,

Dip (Sag) and Swell Measurements

Voltage Swell (rms swell)
Measurement Type............................................. True rms (one cycle calculation by overlapping each half cycle)
Displayed Data ................................................... Amplitude and duration of swell
Measurement Accuracy ...................................... Same as rms voltage
Voltage Dip (RMS sag)
Measurement Type............................................. True rms (one cycle calculation by overlapping each half cycle)
Displayed Data ................................................... Amplitude and duration of dip or interruption
Measurement Accuracy ...................................... Same as rms voltage
Voltage Dropout (Interruption)
Measurement Type............................................. Same as Voltage Dip

Power and PF Measurement

Calculated per IEEE1459 for best performance when distortions exist
Measurement Type............................................. True rms calculated continuously: every cycle, and every 10 or 12
Measurement Accuracy ...................................... ± 0.2 % reading ± 0.1 % full scale + current sensor accuracy
Frequency
Measurement Range .......................................... 42.5 to 69 Hz
Measurement Source ......................................... Same as PLL synchronization source
Measurement Accuracy ...................................... ± 10 mHz (10 to 110 % of range, with sine wave)
Reactive Power
Accuracy ............................................................. ± 0.2% reading ± 0.1 % full scale + current sensor accuracy
Power Factor
Measurement Range .......................................... -1.000 (leading) to 0.000 to +1.000 (lagging)
Measurement Accuracy ...................................... ± 1 digit from the calculation of each measured value (± 3 digits for
Displacement Power Factor
Measurement Method......................................... Calculated from the phase difference between voltage fundamental
Measurement Range .......................................... -1.000 (leading) to 0.000 to + 1.000 (lagging)
Measurement Accuracy ...................................... ± 0.5 % reading ± 2 % full scale ± 1 digit
Voltage Unbalance and Phase Sequence
Measurement Method......................................... Positive sequence voltage divided by negative sequence voltage, per
Harmonic Voltage and Current
Analysis Window................................................. rectangular
Analysis Order .................................................... 1st to 50th order
Measurement Accuracy ...................................... Voltage / Current: 1st to 20th orders: ± 0.5 % reading ± 0.2 % full scale
Measurement Method ......................................... IEC 61000-4-7:2002
Inter-harmonic Voltage and Current (Intermediate Harmonics)
Analysis Window................................................. rectangular
Analysis Orders .................................................. 0.5 to 49.5th order
Measurement Method ......................................... IEC 61000-4-7:2002
Specifications for the System: Recorder and Power Analyze Software
100 kHz)
(voltage between lines is measured for 3P3W lines and phase voltage
is measured for 3P4W lines)
(voltage between lines is measured for 3P3W lines and phase voltage
is measured for 3P4W lines)
cycles at 50 or 60 Hz respectively, as required by standards
total)
and current fundamental
IEC 61000-4-30
21st to 50th orders: ± 1 % reading ± 0.3 % full scale (current sensor
accuracy must be included for current and power)