Installation
Figure 58. Typical through-the-base gas installation
Requirements for Gas Heat
Note: The unit gas train and optional through-the-base
gas shut-off valve are rated at 1/2 PSIG maximum.
A pressure reducing regulator is recommended to
prevent this maximum from being exceeded.
These components must be isolated during field
gas piping test that exceed 1/2 PSIG. It is
recommended that the field piping be capped prior
to the unit gas train or optional through-the-base
gas shut-off valve if present.
•
Gas supply line properly sized and connected to the
unit gas train.
•
All gas piping joints properly sealed.
•
Gas piping leak checked with a soap solution. If piping
connections to the unit are complete, do not pressurize
piping in excess of 0.50 psig or 14-inch wc to prevent
component failure.
•
Drip leg Installed in the gas piping near the unit.
•
Minimum gas supply pressure should be 4.5-inch wc.
Figure 59. Manifold pressure tap location
32
6 1/2" (165 MM) Pipe Nipple
90° Elbow
5" (127 MM) Pipe Nipple and Union
Modulating
Valve
Tap Location to Obtain Manifold
Pressure for Modulating Gas Heaters
Gas Shut-Off Valve
and Street Elbow
90° Elbow
and Nipples
•
Minimum gas supply pressure for modulating "V"
models should be 5.5-inch wc.
•
Maximum gas supply pressure must not exceed 14.0-
inch wc.
•
Manifold pressure for single stage heaters should be
set to 3.3-inch wc.
•
Manifold pressure for two stage heaters should be set
to 3.5-inch wc on high fire and 1.8-inch wc on low fire.
Note: Manifold pressure not applicable for units with
Low NOx gas furnace option. Manifold pressure is
not utilized as an adjustment/checking parameter
for this system.
•
Manifold pressure for modulating heaters is 3.5-inch
wc at high fire.
Note: Modulating valve must have 10 Vdc signal voltage
to achieve high fire. See the following image for
manifold pressure tap location.
•
Flue exhaust clear of any obstruction.
Adjust Manifold
Pressure Here
Main Gas Valve
RT-SVX46G-EN