LOOP BATTERY CALCULATOR
It is strongly recommended that the 'Loop Battery
calculator' is used to ensure that an INSPIRE system
design will operate correctly. It is used to obtain accurate
loop loading results.
'SENSOR DEVICES' ON A LOOP
A Sensor device such as a Smoke or Heat detector:
is given a unique 'Address'.
can be given a location label of up to 64 characters
(Label texts on ID3K are limited to 32 characters)
associated with a 'Detection Zone'
has a working LED indicator on each device,
a Remote LED option
operating at particular Sensor sensitivity profiles.
'MODULE DEVICES' ON A LOOP
A Module device such as a Input/Output Interface,
Sounder-Strobe, Mains switching module, FAAST LT
Interface, and MCP etc on a loop:
is given a unique 'Address'
can be given a location label of up to 64 characters
(Label texts on ID3K are limited to 32 characters)
with a working LED indicator
an I/O channel can each be given a label.
Output channel can be set to 'Control Output channel'
or 'Fire Alarm Output channel'
Input channel can be set to 'Control Input channel',
y
'Fire Detection Input channel', 'Technical Alarm Input
Notifier INSPIRE E10/E15 Control Panels - Installation instructions
channel' or 'Fault input channel'
Module's Input or Output 'channel' can be
y
associated with 'Detection Zone', 'Alarm Zone'
or 'Control Zone'.
Zone Monitor can be set to 'Detector', 'MCP',
y
'Sprinkler', 'Mixed' or 'Other Type'
a FAAST LT has channel(s) that monitor the
y
status of loop ASD sensor(s)
Where required, the channel 'Function type'
y
can be set to 'Control', 'Sounder', 'Strobe', 'Fire
Protection' or 'Fire Routing'
'Monitoring Type' can be an End-of-Line from
y
a range, with or without a delayed operation
and can be set as a latching input
- Output can be relay contacts set to either
Normally Open or Normally Closed
- Output 'Application Type' can be set to
'General Purpose', Fire Protection
installation', 'Annunciation' or 'Fire
Extinguishing'
47