Honeywell Notifier INSPIRE E10 Installation Instructions Manual page 19

Fire alarm control panels
Hide thumbs Also See for Notifier INSPIRE E10:
Table of Contents

Advertisement

Battery current with mains disconnected is dependent on the system configuration and current during alarm.
Battery charging Current: 0.8 A (12 Ah), 1.6 A (24 Ah) and 2.5 A (38 Ah)
Battery end of discharge Voltage / Deep discharge protection : 21 V (U
Output Voltage at which the outputs are switched off: 24 V
Battery voltage
at which outputs are switched off: 21 V
ENVIRONMENTAL
Climatic Classification: 3K5, (IEC 721-2-3)
Operating Temperature: -5 °C to +40 °C
Relative Humidity: 5 % to 95 % non-condensing
Height above sea level: 2000 m maximum
Panel Sealing: IP30 (EN60529)
EMC Emissions: EN61000-6-3 Residential, Commercial & Light Industry
Immunity: EN50130-4 Alarm systems: Electromagnetic compatibility
Product family standard: Immunity requirements for components of fire, intruder and social alarm systems
Safety: EN 62368-1.