C.2

Validation error with data record 100

The technology module checks the transferred data record. If the technology module detects
invalid or inconsistent values, it outputs an error code (STATUS output parameter of the
WRREC/RDREC instruction). You can find information on using WRREC/RDREC in the section
Parameter validation error with data record 128 (Page 61).
Error codes
The following table shows the module-specific error codes and their meaning for data record
100.
Error code in the
STATUS parameter (hexadec-
imal)
Byte
Byte
Byte
Byte
0
1
2
3
DF
80
B0
00
DF
80
B1
01
DF
80
B2
00
DF
80
A7
00
DF
80
A9
00
DF
80
D4
00
Technology module TM FAST (6ES7554-1AA00-0AB0)
Equipment Manual, 04/2023, A5E52301130-AA
Meaning
Data record number unknown
Length of data record incorrect
Slot invalid or not accessible
New command not yet possible because previ-
ous command is still being processed
"Command" parameter invalid
Wrong version
Data record TMFASTControlREC
C.2 Validation error with data record 100
Remedy
Enter valid number for data record
Enter valid value for data record length.
Check whether module is inserted or removed.
Check assigned values for parameters of the
WRREC/RDREC instruction.
Wait until new command is possible (read Byte 1 Bit
4).
Enter valid parameter value.
Check byte 0.
Enter valid values.
67