Operation
8.5 Functions
Parameter
p4078[1]
Setting for the y coordinate in V or mA of the first point on the scaling characteristic.
When analog output 1 is set as a voltage output (p4076[1] = 1 / 4) and terminals X522: 6,5 are used, the
unit is V.
When analog output 1 is set as a current output (p4356[1] = 0 / 2 / 3) and terminals X522: 4,5 are used,
the unit is mA.
Parameter
p4079[1]
Setting for the x coordinate in % of the second point on the scaling characteristic.
Parameter
p4080[1]
Setting for the y coordinate in V or mA of the second point on the scaling characteristic.
When analog output 1 is set as a voltage output (p4076[1] = 1 / 4) and terminals X522: 6,5 are used, the
unit is V.
When analog output 1 is set as a current output (p4356[1] = 0 / 2 / 3) and terminals X522: 4,5 are used,
the unit is mA.
Example: Changing analog output 0 from current to voltage output ± 10 V and setting the characteristic
118
Value
Analog outputs, characteristic value y1
Value
Analog outputs, characteristic value x2
Value
y2 of the characteristic of the analog out‐
puts
Voltage output present at terminal 1, ground is at terminal 2
Set TM31.AO_type [analog output 0] to between -10 and +10
V
Set TM31.AO_char. x1 to 0.00 %.
Set TM31.AO_char. y1 to 0.000 V.
Adjustment range
-20.000 to +20.000 V or mA
Factory setting: 0.000 mA
Adjustment range
-1000.00 to +1000.00%
Factory setting: 100.00 %
Adjustment range
-20.000 to +20.000 V or mA
Factory setting: 20.000 mA
SINAMICS SM150 6SL3845-7NN46-7AA2
Operating Instructions Rev.201910281345 EXAMPLE